LC1D32 (TeSys D, 32 A)

Schneider / Telemecanique · IEC · 3-pole

All contactors

LC1D32 (TeSys D, 32 A)

Schneider / Telemecanique · D-line D09–D38 frame

32 A AC-3 / 15 kW @ 400 V. Covers 10 HP @ 230 V and 20–25 HP @ 460 V three-phase — common on 15–25 HP rotary screw packages.

Ratings
AC-3 @ 400 V
32 A (15 kW)
AC-1 (resistive)
50 A
Hp (3Φ)
≈ 10 HP @ 230 V · 20–25 HP @ 460 V · 30 HP @ 575 V
Three-phase HP
≈ 10 HP @ 230 V · 20–25 HP @ 460 V · 30 HP @ 575 V
Coil data
Available coil voltages
B7/G7/P7/U7/V7 suffix system
Inrush VA
≈ 70 VA (60 Hz)
Sealed (holding) VA
≈ 7–8.5 VA
Pickup voltage
85–110% of rated
Dropout voltage
20–75% of rated
Typical measured coil resistance (±15%, ballpark)
120 VAC (G7)≈ 130–220 Ω
230 VAC (P7)≈ 500–850 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (120 VAC (G7) table value)130 Ω220 Ω
Generic mid-frame 110–120 VAC60 Ω180 Ω

Readings 2× high usually mean heat damage and a coil near end of life. Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: 1/3/5 in, 2/4/6 out; lugs to 8 AWG
Auxiliary contacts: 1 NO built in; LADN blocks to 4 more
Companion overload: LRD32 (23–32 A) or LRD35 (30–38 A)
Cross-references
Field notes
  • At this size, contact wear shows as discolored load-side lugs first — an IR camera sweep finds a failing pole before it welds.
  • Wye-delta sets on screws use three of this family: line, delta, and wye (wye can often be one size smaller).