LC1D95 (TeSys D, 95 A)
Schneider / Telemecanique · D-line D80–D95 frame
95 A AC-3 / 45 kW @ 400 V — 60–75 HP @ 460 V territory. Big copper, replaceable contacts, and a coil that needs a healthy control circuit.
Ratings
- AC-3 @ 400 V
- 95 A (45 kW)
- AC-1 (resistive)
- 125 A
- Hp (3Φ)
- ≈ 30 HP @ 230 V · 60–75 HP @ 460 V · 75 HP @ 575 V
- Three-phase HP
- ≈ 30 HP @ 230 V · 60–75 HP @ 460 V · 75 HP @ 575 V
Coil data
- Available coil voltages
- B7/G7/P7/U7/V7 suffix system
- Inrush VA
- ≈ 200–260 VA
- Sealed (holding) VA
- ≈ 20–26 VA
- Pickup voltage
- 85–110% of rated
- Dropout voltage
- 20–75% of rated
Typical measured coil resistance (±15%, ballpark)
120 VAC (G7)≈ 45–80 Ω
230 VAC (P7)≈ 170–300 Ω
OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.
Coil resistance checker
Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.
Ω
This model (120 VAC (G7) table value)45 Ω–80 Ω
Generic mid-frame 110–120 VAC60 Ω–180 Ω
Readings 2× high usually mean heat damage and a coil near end of life. Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.
Terminals & accessories
Power/coil terminals: 1/3/5 in, 2/4/6 out; lugs to 2/0 AWG
Auxiliary contacts: 1 NO + 1 NC built in; LADN blocks
Companion overload: LR9D/LR9F electronic or LA9D mounting with LRD-class relays
Cross-references
- ABB AF96
- Siemens 3RT2037/38
- Allen-Bradley 100-C85
- Eaton XTCE095F
- WEG CWB95
Field notes
- Contacts and arc chutes are replaceable on this frame — a contact kit beats a full contactor when the coil is still healthy.
- Measure coil current when energized: a coil drawing well above sealed VA/√V has shorted turns and will fail soon.