LC1D95 (TeSys D, 95 A)

Schneider / Telemecanique · IEC · 3-pole

All contactors

LC1D95 (TeSys D, 95 A)

Schneider / Telemecanique · D-line D80–D95 frame

95 A AC-3 / 45 kW @ 400 V — 60–75 HP @ 460 V territory. Big copper, replaceable contacts, and a coil that needs a healthy control circuit.

Ratings
AC-3 @ 400 V
95 A (45 kW)
AC-1 (resistive)
125 A
Hp (3Φ)
≈ 30 HP @ 230 V · 60–75 HP @ 460 V · 75 HP @ 575 V
Three-phase HP
≈ 30 HP @ 230 V · 60–75 HP @ 460 V · 75 HP @ 575 V
Coil data
Available coil voltages
B7/G7/P7/U7/V7 suffix system
Inrush VA
≈ 200–260 VA
Sealed (holding) VA
≈ 20–26 VA
Pickup voltage
85–110% of rated
Dropout voltage
20–75% of rated
Typical measured coil resistance (±15%, ballpark)
120 VAC (G7)≈ 45–80 Ω
230 VAC (P7)≈ 170–300 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (120 VAC (G7) table value)45 Ω80 Ω
Generic mid-frame 110–120 VAC60 Ω180 Ω

Readings 2× high usually mean heat damage and a coil near end of life. Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: 1/3/5 in, 2/4/6 out; lugs to 2/0 AWG
Auxiliary contacts: 1 NO + 1 NC built in; LADN blocks
Companion overload: LR9D/LR9F electronic or LA9D mounting with LRD-class relays
Cross-references
  • ABB AF96
  • Siemens 3RT2037/38
  • Allen-Bradley 100-C85
  • Eaton XTCE095F
  • WEG CWB95
Field notes
  • Contacts and arc chutes are replaceable on this frame — a contact kit beats a full contactor when the coil is still healthy.
  • Measure coil current when energized: a coil drawing well above sealed VA/√V has shorted turns and will fail soon.