LC1D09 (TeSys D, 9 A)

Schneider / Telemecanique · IEC · 3-pole (+1NO aux built in on most SKUs)

All contactors

LC1D09 (TeSys D, 9 A)

Schneider / Telemecanique · D-line D09–D38 frame

The world's most common IEC contactor. 9 A AC-3 covers motors to 4 kW/5 HP @ 400 V. Shares the same compact frame with D12–D38, so aux blocks, overloads (LRD) and reversing links all interchange.

Ratings
AC-3 @ 400 V
9 A (4 kW)
AC-1 (resistive)
25 A
Hp (3Φ)
≈ 2 HP @ 230 V · 5 HP @ 460 V · 7.5 HP @ 575 V
Hp (1Φ)
≈ ⅓ HP @ 115 V · 1 HP @ 230 V
Mechanical life
≈ 15 million operations
Single-phase HP
≈ ⅓ HP @ 115 V · 1 HP @ 230 V
Three-phase HP
≈ 2 HP @ 230 V · 5 HP @ 460 V · 7.5 HP @ 575 V
Coil data
Available coil voltages
Suffix codes: B7 24V · G7 120V · P7 230V · U7 240V · V7 400V (see coil-code table)
Inrush VA
≈ 70 VA (60 Hz)
Sealed (holding) VA
≈ 7–8.5 VA
Pickup voltage
85–110% of rated coil voltage
Dropout voltage
20–75% of rated
Typical measured coil resistance (±15%, ballpark)
24 VAC (B7)≈ 5–9 Ω
120 VAC (G7)≈ 130–220 Ω
230 VAC (P7)≈ 500–850 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (24 VAC (B7) table value)5 Ω9 Ω
Generic small-frame 24 VAC8 Ω16 Ω

OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: Power: 1/L1, 3/L2, 5/L3 in top — 2/T1, 4/T2, 6/T3 out bottom. Coil A1/A2 (A2 duplicated top and bottom). Spring or screw-clamp versions.
Auxiliary contacts: 1 NO built in (terminal 13/14); add LADN front blocks (up to 4 more) or LA8N side blocks
Companion overload: LRD08 (2.5–4 A) or LRD06/LRD07 below that; clips directly under the contactor
Cross-references
Field notes
  • A2 appears on BOTH top and bottom — they're the same node, a jumper convenience, not two coils.
  • Coil is field-replaceable on D-line: two clips and it slides off. Match the voltage code exactly.
  • Green LED add-on (LAD9) is a cheap way to see control state from across the room.
Manufacturer documentation