CWB32 (3-pole 32 A)

WEG · IEC · 3-pole

All contactors

CWB32 (3-pole 32 A)

WEG · CWB 22–38 A frame (45 mm)

32 A CWB — the top of the 45 mm frame. Standard line contactor on 20 HP 460 V screws and delta contactor on 30–40 HP wye-delta sets.

Ratings
AC-3 (440 V)
32 A
AC-1 (resistive)
50 A
Hp (3Φ)
10 HP @ 230 V · 20 HP @ 460 V
Mechanical life
≈ 10 million operations
Three-phase HP
10 HP @ 230 V · 20 HP @ 460 V
Coil data
Available coil voltages
24, 110–120, 208–240, 380–415, 440–480, 550–600 VAC; 24 VDC
Inrush VA
≈ 130 VA
Sealed (holding) VA
≈ 11 VA
Pickup voltage
≥ 80% of rated
Dropout voltage
≈ 30–60% of rated
Typical measured coil resistance (±15%, ballpark)
24 VAC≈ 4–10 Ω
120 VAC≈ 100–220 Ω
240 VAC≈ 450–850 Ω
480 VAC≈ 1,800–3,400 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (24 VAC table value)4 Ω10 Ω
Generic mid-frame 24 VAC4 Ω9 Ω

OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: Box lug to 25 mm² / 4 AWG; coil A1/A2 front
Auxiliary contacts: 1 built-in; expandable to 5 with front + side blocks
Companion overload: RW67D thermal (22–32 A range) or RW17 electronic relay
Cross-references
Field notes
  • In a wye-delta panel this frame is usually the delta (run) contactor — it carries 0.58 × FLA continuously, so a hot body here means the transition timer is out of adjustment.
  • Torque the box lugs to the label value and re-check after the first heat cycle; loose lugs on this frame are the #1 cause of a burnt T-terminal.
  • Chattering on start with good coil resistance points at control-transformer sag, not the contactor.
WEG resources

Links go to the manufacturer's current catalog or product page — model-specific pages are often retired, so these stay live.

Manufacturer documentation