CWB95 (3-pole 95 A)
WEG · CWB 80–95 A frame
Top of the compact CWB range — covers 25–60 HP compressors and wye-delta line/delta duties. Beyond this frame WEG steps to the CWB125+ and CWBS safety-rated variants for safety-circuit duty.
Ratings
- AC-3 (440 V)
- 95 A
- AC-1 (resistive)
- 110 A
- Hp (3Φ)
- 30 HP @ 230 V · 60 HP @ 460 V
- Three-phase HP
- 30 HP @ 230 V · 60 HP @ 460 V
Coil data
- Available coil voltages
- Suffix-coded coil: 24, 120, 208–240, 480 VAC 50/60 Hz; electronic wide-range options
- Inrush VA
- ≈ 350 VA
- Sealed (holding) VA
- ≈ 22 VA
- Pickup voltage
- ≥ 80% of rated
- Dropout voltage
- ≈ 40–65% of rated
Typical measured coil resistance (±15%, ballpark)
24 VAC≈ 3–7 Ω
120 VAC≈ 40–90 Ω
480 VAC≈ 600–1,100 Ω
OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.
Coil resistance checker
Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.
Ω
This model (24 VAC table value)3 Ω–7 Ω
Generic mid-frame 24 VAC4 Ω–9 Ω
OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.
Terminals & accessories
Power/coil terminals: L1–L3 top, T1–T3 bottom; lug terminals to 50 mm² / 1/0 AWG; coil front
Auxiliary contacts: 2 built-in aux (NO+NC); front and side blocks expand to 6 total
Companion overload: RW117 thermal overload (separate-mount on this frame); or electronic motor protection relay for wye-delta
Cross-references
- Schneider LC1D80 / LC1D95
- Siemens 3RT2046 (S3)
- ABB AF96
- Allen-Bradley 100-C85
- Eaton XTCE095F
- Legacy: WEG CWM95 / CWM112
Field notes
- In wye-delta sets, size the delta contactor at 0.58 × motor FLA and the wye contactor at 0.33 × — a like-for-like 95 A on all three is oversized but safe.
- For safety-circuit (mirror-contact) applications, spec the CWBS variant — the standard CWB aux contacts are not mechanically linked per IEC 60947-4-1 Annex F.
- Coil inrush ≈ 350 VA will sag a marginal control transformer — size the transformer for inrush, not sealed VA.