SC-E3 (3-pole 32 A)

Fuji Electric · IEC · 3-pole

All contactors

SC-E3 (3-pole 32 A)

Fuji Electric · SC-E series, 54 mm frame

Fuji SC-E3 magnetic contactor — the standard fitment in Japanese-built compressors, vacuum pumps and machine tools (Hitachi, Anest Iwata, Orion packages).

Ratings
AC-3 (440 V)
32 A
AC-1
50 A
Hp (3Φ)
10 HP @ 230 V · 20 HP @ 460 V
Three-phase HP
10 HP @ 230 V · 20 HP @ 460 V
Coil data
Available coil voltages
24, 100–110, 200–220, 380–440 VAC 50/60 Hz; DC operated variants
Inrush VA
≈ 120 VA
Sealed (holding) VA
≈ 11 VA
Pickup voltage
0.85–1.1 × rated
Dropout voltage
0.2–0.6 × rated
Typical measured coil resistance (±15%, ballpark)
24 VAC≈ 4–10 Ω
100/110 VAC≈ 90–200 Ω
200/220 VAC≈ 400–800 Ω
400/440 VAC≈ 1,600–3,100 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (24 VAC table value)4 Ω10 Ω
Generic mid-frame 24 VAC4 Ω9 Ω

OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: Box lug / finger-protection terminals; DIN or screw mount
Auxiliary contacts: Built-in aux per suffix; SZ-A series add-on blocks
Companion overload: TR-E / TK-E thermal overload relay direct-mount
Cross-references
Field notes
  • Japanese machines commonly use 200 V coils on 208/230 V control — a 200 V coil on 240 V runs hot and shortens life.
  • TR-E overload dials are in amps at 50/60 Hz; verify frequency-derating before setting on 60 Hz service.
  • SC-E and older SC-N accessories are not interchangeable; confirm the series before ordering aux blocks.
Manufacturer documentation