CWB50 (3-pole 50 A)

WEG · IEC · 3-pole

All contactors

CWB50 (3-pole 50 A)

WEG · CWB 40–65 A frame (55 mm)

50 A CWB for 25–30 HP 460 V compressors. Same frame and accessories as the CWB40/CWB65, so all three interchange mechanically.

Ratings
AC-3 (440 V)
50 A
AC-1 (resistive)
80 A
Hp (3Φ)
15 HP @ 230 V · 30 HP @ 460 V
Short-circuit (type 2)
Per RW/MPW coordination tables
Three-phase HP
15 HP @ 230 V · 30 HP @ 460 V
Coil data
Available coil voltages
24, 110–120, 208–240, 380–415, 440–480 VAC; electronic wide-range options
Inrush VA
≈ 200 VA
Sealed (holding) VA
≈ 16 VA
Pickup voltage
≥ 80% of rated
Dropout voltage
≈ 40–65% of rated
Typical measured coil resistance (±15%, ballpark)
24 VAC≈ 3–8 Ω
120 VAC≈ 60–130 Ω
240 VAC≈ 250–520 Ω
480 VAC≈ 900–1,900 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (24 VAC table value)3 Ω8 Ω
Generic mid-frame 24 VAC4 Ω9 Ω

OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: L1–L3 top / T1–T3 bottom, lug to 35 mm² / 2 AWG
Auxiliary contacts: 2 built-in (1NO+1NC); front and side blocks to 6 total
Companion overload: RW67D or separate-mount RW117 thermal; MPW manual motor protector alternative
Cross-references
  • Schneider LC1D50
  • Siemens 3RT2036
  • ABB AF52
  • Allen-Bradley 100-C55
  • Eaton XTCE050D
  • Legacy WEG CWM50
Field notes
  • If the panel originally had a CWM50, the CWB50 is the direct current-line replacement — but the accessory blocks are NOT interchangeable between CWM and CWB.
  • Above about 40 A, order the electronic coil for generator-fed or long-feeder sites; the AC magnet coil chatters under a 15% dip.
  • Sealed VA is small but inrush ≈ 200 VA — a 50 VA control transformer will not hold this in.