CWB125 (3-pole 125 A)

WEG · IEC · 3-pole

All contactors

CWB125 (3-pole 125 A)

WEG · CWB 80–125 A frame

Largest of the CWB IEC line at 125 A AC-3 — 75 HP @ 460 V. Above this WEG moves to the CWM150+ / CWMH range.

Ratings
AC-3 (440 V)
125 A
AC-1 (resistive)
150 A
Hp (3Φ)
40 HP @ 230 V · 75 HP @ 460 V
Three-phase HP
40 HP @ 230 V · 75 HP @ 460 V
Coil data
Available coil voltages
24, 110–120, 208–240, 380–415, 440–480 VAC; electronic wide-range standard on many part numbers
Inrush VA
≈ 400 VA
Sealed (holding) VA
≈ 25 VA
Pickup voltage
≥ 80% of rated
Dropout voltage
≈ 40–65% of rated
Typical measured coil resistance (±15%, ballpark)
120 VAC≈ 35–80 Ω
480 VAC≈ 550–1,100 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (120 VAC table value)35 Ω80 Ω
Generic mid-frame 110–120 VAC60 Ω180 Ω

Readings 2× high usually mean heat damage and a coil near end of life. Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: Bus-bar / lug to 95 mm² / 3/0 AWG
Auxiliary contacts: 2 built-in; up to 6 with blocks
Companion overload: Electronic motor protection relay recommended at this size
Cross-references
  • Schneider LC1D115/LC1D150
  • Siemens 3RT2046/3RT1054
  • ABB AF116
  • Allen-Bradley 100-C120
  • Eaton XTCE115G
Field notes
  • At 125 A, cable termination torque and lug material (Al vs Cu) matter more than the contactor — re-torque annually.
  • Wye-delta sets: line and delta at 0.58 × FLA, wye at 0.33 × FLA — a matched trio of CWB125s is over-spec but common on OEM panels.
  • Feel the body after an hour of run time; anything you can't hold your hand on means a loose connection or an undersized frame.
WEG resources

Links go to the manufacturer's current catalog or product page — model-specific pages are often retired, so these stay live.

Manufacturer documentation