Line / sump pressure transducer (4–20 mA)

Generic / universal · Sensor

All components

Two-wire loop-powered transducer supplying sump and line pressure to the controller.

Also called: pressure transmitter · sump transducer

How it works

A strain-gauge or ceramic cell converts pressure to a 4–20 mA current proportional to the span. 4 mA = 0 pressure, 20 mA = full span. Loop-powered from the controller's 24 VDC supply.

Specifications

Supply
12 – 30 VDC loop
Signal
4 mA = 0 %, 12 mA = 50 %, 20 mA = 100 % of span
Common spans
0 – 200 PSI, 0 – 232 PSI (16 bar), 0 – 300 PSI
Loop resistance
Do not exceed the transmitter's max load (often 500 – 600 Ω at 24 V)

Parts you can order

  • Danfoss
    MBS 3000 pressure transmitter
    060G1133 (0–232 psi, 4–20 mA, 1/4 in. NPT)
    $130 – $320
  • Danfoss
    MBS 3000 pressure transmitter
    MBS 3000, 0–500 psi range code
    $150 – $360
  • Danfoss
    MBS 3000 pressure transmitter
    060G1133 (0–232 psi, 4–20 mA)
    $130 – $300
  • WIKA
    A-10 pressure transmitter
    A-10 (configure range/output)
    $150 – $340
  • Gems Sensors
    3100 series transducer
    3100 (configure range/output)
    $160 – $360
  • Ashcroft
    G2 pressure transducer
    G2 (configure range/output)
    $180 – $400
Open the full parts database →

Field test procedure

  1. Break the loop and read mA in series, or measure across the controller's sense resistor.
  2. Compare mA against a calibrated gauge: mA = 4 + 16 × (reading ÷ span).
  3. Below 3.8 mA or above 20.5 mA = sensor fault or wiring fault, not a real pressure.
  4. Never megger a transducer loop — you will destroy the cell.

Symptoms & probable causes

  • Pressure reads 0 with the machine running
    Open loop, reversed polarity, or a blocked sensing port.
  • Pressure reads full scale
    Shorted loop or a failed cell.