Sigma Air Manager 4.0 (SAM 4.0)

Kaeser

AirCompDX - Field Reference for Air Compressor Techs

Sigma Air Manager 4.0 (SAM 4.0)

Plant master, not a compressor controller — pairs with Sigma Control 2 on each machine. Best-in-class for multi-unit Kaeser fleets.

Manufacturer
Kaeser
Display
12-inch color touchscreen with adaptive 3D pressure-band control.
Years produced
~2016 – present.
Power supply
24 VDC, 12-inch color touchscreen master controller.
Ambient range
0 – 40 °C in enclosure.
Protection rating
IP54 front.
Relay outputs
Distributed via Sigma Network to each compressor — SAM 4.0 itself is primarily an IP master.
Replaces
Sigma Air Manager (original / SAM 8/16)
Used on
  • Kaeser plants with 2+ compressors (up to 16)
  • Retrofits on mixed Kaeser / non-Kaeser fleets via Sigma Network
Features
  • Adaptive 3D control — optimizes across pressure, energy, service intervals
  • Predictive maintenance dashboard
  • Energy KPI logging & auditor-friendly reports
  • SIGMA SMART AIR remote monitoring
Interfaces
  • Ethernet (Sigma Network to compressors)
  • Modbus TCP / Profinet / EtherNet/IP (upstream to plant BMS)
  • OPC UA server (option)
  • USB & SD data logging
Sensor inputs
  • Multiple line pressure transducers
  • Flow (option)
  • Dewpoint (dryer skid)
  • Power meters (SAM Logistics option)
Common fault codes
First checks
  • Verify Ethernet cable & switch
  • Check compressor controller is powered & on network
  • Re-scan network in SAM setup
First checks
  • Confirm 4–20 mA loop
  • Isolate & verify transducer with hand pump

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Wiring notes
  • Dedicated managed Ethernet switch for Sigma Network — do NOT share with plant LAN
  • Static IPs per compressor set in each controller
  • Isolate BMS Modbus/Profinet with a firewall or gateway
Known issues & field notes
  • Firmware upgrades require matched Sigma Control 2 firmware on downstream units
  • Confusing when third-party compressors are added via dry-contact only — you lose predictive features on those units

User levels: Operator, Technician, Service. Default technician PIN is often 12345 on new commissioning but IS typically changed. Service level is Kaeser-only.

Manuals & literature
Kaesersupport portal

Manuals gated — request via local rep or parts portal