| System | Line-line | Line-neutral | Notes |
|---|---|---|---|
| 120/240 1Φ | 240 V | 120 V | Small recips ≤5 HP |
| 208Y/120 3Φ | 208 V | 120 V | Light commercial; motors run hot |
| 240Δ 3Φ | 240 V | 120/208* | *High-leg B = 208 V to ground |
| 480Y/277 3Φ | 480 V | 277 V | Most industrial compressors |
| 600Y/347 3Φ | 600 V | 347 V | Canada |
Utilization voltage tolerance: ±10% of nameplate. A 460 V motor on a 480 V system is normal; a 460 V motor seeing 415 V is not.
Reduced-voltage starting by first connecting the motor windings in wye (33% of full voltage across each winding, ~33% starting current and torque), then transitioning to delta for run.
- Start (S contactor): wye-point of motor leads T4-T5-T6 tied together. Line contactor (M) energizes T1-T2-T3.
- Run (D contactor): after timer (0.5-2.5 s), S drops out, D pulls in — T4→T3, T5→T1, T6→T2 (per nameplate).
- Mechanical interlock: S and D must NEVER be in at the same time — phase-to-phase short.
- Overload sizing: heater = motor FLA × 0.58 (line current in the delta winding).
Simplest start. Single contactor + overload. Inrush typically 600-800% FLA. Acceptable up to ~10-15 HP on most utilities; check utility rules above that.
SCR-based reduced voltage. Replaces wye-delta in modern installs. Adjustable ramp time, current limit, and kick-start. No moving parts in the start circuit.
- Typical setup: current limit 300-400% FLA, ramp 5-15 s, kick-start off unless the pump won't break away.
- Bypass contactor closes at full voltage — if it fails, SCRs cook. Check bypass aux feedback on nuisance overtemp faults.
- Shorted SCR reads continuity phase-to-phase with the unit off — the motor will single-phase or creep.
Best for variable-demand screw compressors. Modulates motor speed to match air demand. Always use inverter-duty motor or check insulation rating. Shielded VFD cable, proper grounding, and dV/dt or sine filter for long runs.
- Never put a contactor between drive and motor while running, and never PF-correct on the motor side.
- Keep motor cable under ~50 ft unshielded / 100 ft shielded before adding a load reactor or dV/dt filter.
- Bearing fluting on non-inverter motors ⇒ add a shaft grounding ring; look for frosted/washboard races.
- Common faults: OU (overvoltage on decel — extend decel/add brake resistor), OC (short decel or output short), OH (blocked heatsink filter).
- Min speed matters — screw airends need ~20-30% minimum for oil pressure and cooling.
Always follow the nameplate/connection plate — brands vary. Rotation reverses by swapping any two line leads.
- CSIR/CSCR: start cap (high µF, short duty, black case) drops out via centrifugal switch or potential relay; run cap (low µF, metal oval, continuous).
- Cap sizing: replace within ±10% µF for run caps, and use equal-or-slightly-higher µF and ≥ same voltage for start caps.
- Motor hums, won't start, spins if nudged ⇒ open start cap, failed start switch/relay, or stuck unloader.
- Test caps with a meter on µF, discharged, one lead lifted. Bulged top or leaking = replace.
- NEMA size by max FLA at applied voltage; IEC by AC-3 rating.
- Chattering ⇒ low coil voltage (<85% rated). Check transformer & wire length.
- Welded tips ⇒ jogging / undersized / arcing on opening. Replace, don't file.
- Burned line lugs ⇒ loose terminations. Torque to spec, IR scan annually.
- Standard: 115% of motor FLA (NEC 430.32). 125% max for marked SF≥1.15.
- Class 10 = trip ≤10 s at 600% (general). Class 20 = 20 s (high-inertia). Class 30 rarely needed for compressors.
- Ambient compensation matters in hot rooms — use ambient-compensated OL.
Full FLC tables, wire size, and starter picks are in the Motor Data calculator.
- HP / kW — output mechanical power.
- FLA — full-load amps at rated voltage.
- SF — service factor (1.0 standard, 1.15 = 15% short-term overload OK).
- Code letter — locked-rotor kVA/HP (A lowest, V highest). Code G typical for compressor TEFC motors.
- Insulation class — B (130°C), F (155°C), H (180°C). Run cooler = longer life (halves every 10°C above rated).
- NEMA design — B (general), C (high starting torque, good for recip compressors with unloaders).
- Winding continuity: 3Φ — all three should read within 5-10% of each other.
- Winding to ground: >1 MΩ minimum (megger at 500/1000 VDC).
- Voltage balance (3Φ): max deviation <1% of average. 2% causes ~8% temp rise.
- Current balance: max deviation <10% of average under load.
| Symptom | Check first |
|---|---|
| Trips instantly on start | Shorted winding, welded contactor, wrong OL setting, locked airend |
| Trips after minutes | OL undersized, high ambient, high discharge pressure, loose lug heating |
| Hums, no rotation | Single-phasing (blown fuse / open contact), start cap (1Φ), seized rotor |
| Unbalanced amps | Loose termination, bad contact tip, unbalanced supply voltage |
| Breaker trips, OL doesn't | Ground fault or short — megger before re-energizing |
| Control voltage dead | Blown CPT fuse, E-stop, HP switch, thermal switch open |
| Runs backwards | Two lines swapped after service — verify rotation arrow before loading |
| Nuisance drive faults | Loose ground, missing shield bond, cable too long, blocked filter |
- LOTO the disconnect, then verify absent voltage phase-to-phase and phase-to-ground with a tested meter (live-dead-live).
- Bleed receiver and sump pressure before opening any panel that shares a frame with pressurized components.
- VFD DC bus holds charge — wait for the drive's stated discharge time (typically 5-15 min) and confirm bus volts.
- Arc-flash PPE per the equipment label for any energized troubleshooting; 480 V panels are not glove-optional.