Sigma Air Manager 2 (SAM 2 / legacy SAM)

Kaeser

Sigma Air Manager 2 (SAM 2 / legacy SAM)

If a plant is already running SAM 2 with mixed-vintage machines, confirm each machine's interface card before quoting a SAM 4.0 upgrade — the interface, not the master, usually drives the cost.

Manufacturer
Kaeser
Display
Monochrome graphic display with membrane keys (SAM 8/16 variants by machine count).
Years produced
~2004 – 2015. Superseded by Sigma Air Manager 4.0.
Power supply
100 – 240 VAC wall-mount enclosure, internal 24 VDC bus.
Ambient range
0 – 45 °C.
Protection rating
IP54 wall enclosure.
Relay outputs
Per-compressor enable relays, dryer enable, common alarm.
Replaced by
Sigma Air Manager 4.0
Used on
  • Mixed Kaeser fleets
  • Third-party compressors via contact interface
Features
  • 3-Dadvanced control — pressure band, run hours and switching losses balanced together
  • Up to 8 or 16 compressors depending on model
  • Trend and energy logging exportable for audits
  • Remote alarm relay and modem callout on legacy builds
Interfaces
  • Profibus DP
  • Modbus RTU
  • Ethernet (later builds)
  • Volt-free contacts
Sensor inputs
  • Network pressure (primary and backup)
  • Dew point (option)
  • Compressor status via Profibus or dry contacts
Fault code lookup
First checks
  • Unique address per machine
  • Termination resistors at the two physical ends
  • Check the bus connector switch position
First checks
  • Loop check 4–20 mA
  • Sense line isolation valve
  • Compare with a calibrated gauge
First checks
  • Every machine must be in Remote/SAM mode
  • Check for standing alarms on slaves
  • Verify isolation valves open

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • Profibus requires the correct connector with termination switch — a mis-set switch takes down the whole segment
  • Fit a hardwired backup pressure switch so master failure cannot leave the plant without air
Known issues & field notes
  • Legacy SAM hardware and Profibus cards are increasingly hard to source; most upgrades go to SAM 4.0
  • Older units use a serial service port; a USB-serial adapter with a genuine chipset is required for parameter backup

Operator and service levels set at commissioning by the Kaeser dealer.

Manuals & literature
Kaesersupport portal

Manuals gated — request via local rep or parts portal

Your manuals

Sign in to upload and pin your own PDF manuals to this controller.