Sigma Air Manager 2 (SAM 2 / legacy SAM)
If a plant is already running SAM 2 with mixed-vintage machines, confirm each machine's interface card before quoting a SAM 4.0 upgrade — the interface, not the master, usually drives the cost.
Manufacturer
Kaeser
Display
Monochrome graphic display with membrane keys (SAM 8/16 variants by machine count).
Years produced
~2004 – 2015. Superseded by Sigma Air Manager 4.0.
Power supply
100 – 240 VAC wall-mount enclosure, internal 24 VDC bus.
Ambient range
0 – 45 °C.
Protection rating
IP54 wall enclosure.
Relay outputs
Per-compressor enable relays, dryer enable, common alarm.
Replaced by
Sigma Air Manager 4.0
Used on
- Mixed Kaeser fleets
- Third-party compressors via contact interface
Features
- 3-Dadvanced control — pressure band, run hours and switching losses balanced together
- Up to 8 or 16 compressors depending on model
- Trend and energy logging exportable for audits
- Remote alarm relay and modem callout on legacy builds
Interfaces
- Profibus DP
- Modbus RTU
- Ethernet (later builds)
- Volt-free contacts
Sensor inputs
- Network pressure (primary and backup)
- Dew point (option)
- Compressor status via Profibus or dry contacts
Fault code lookup
First checks
- Unique address per machine
- Termination resistors at the two physical ends
- Check the bus connector switch position
First checks
- Loop check 4–20 mA
- Sense line isolation valve
- Compare with a calibrated gauge
First checks
- Every machine must be in Remote/SAM mode
- Check for standing alarms on slaves
- Verify isolation valves open
First checks
- Replace the backup battery
- Re-enter time and schedule
Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.
Sensor pin resistance & signal values
Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.
Wiring notes
- Profibus requires the correct connector with termination switch — a mis-set switch takes down the whole segment
- Fit a hardwired backup pressure switch so master failure cannot leave the plant without air
Known issues & field notes
- Legacy SAM hardware and Profibus cards are increasingly hard to source; most upgrades go to SAM 4.0
- Older units use a serial service port; a USB-serial adapter with a genuine chipset is required for parameter backup
Operator and service levels set at commissioning by the Kaeser dealer.
Manuals & literature
Kaeser — support portal
Manuals gated — request via local rep or parts portal
Your manuals
Sign in to upload and pin your own PDF manuals to this controller.