Xe-90M

Ingersoll Rand

Xe-90M

The 90M is the usual retrofit target when replacing an obsolete Intellisys SG on an R-Series — sensors change but the panel cutout is close.

Manufacturer
Ingersoll Rand
Display
3.5" backlit graphic LCD with soft keys and status LED bar.
Years produced
~2014 – present. Mid tier of the Xe family.
Power supply
24 VDC from package transformer; battery-backed clock.
Ambient range
0 – 46 °C.
Protection rating
IP54 front.
Relay outputs
Main/star/delta, load, blowdown, dryer enable, common alarm, remote-run, spare programmable relay.
Replaces
Intellisys SG, Xe-70M (on larger frames)
Used on
  • IR R-Series 37–75 kW fixed speed
  • Sierra oil-free (select frames)
  • UP6-Series larger packages
Features
  • Integrated sequencing of up to 4 compressors without an external master
  • Energy-saving 'Progressive Adaptive Control' — reduces unloaded run time automatically
  • Full alarm and event history with hour-stamped entries
  • Dual pressure setpoint with schedule
Interfaces
  • Modbus RTU (RS-485)
  • Ethernet Modbus TCP (option)
  • Volt-free contacts
  • X-Series sequencing link
Sensor inputs
  • Package discharge pressure
  • Sump pressure
  • Airend discharge temp (RTD)
  • Inlet vacuum (option)
  • Separator ΔP
  • Coolant filter ΔP
Fault code lookup
First checks
  • Coolant level
  • Cooler core / aftercooler fouling
  • Thermal valve element
First checks
  • Inlet valve not closing on unload
  • Blowdown solenoid failed closed
  • Check MPV / check valve
First checks
  • Change filter, reset the timer
  • Cold-start ΔP alarms are normal until fluid warms
First checks
  • Confirm control mode is set to Remote
  • Check the remote loop contact stays closed long enough
  • Look for a standing alarm blocking start
First checks
  • Inlet valve stuck closed
  • Blowdown valve leaking
  • Verify sump transducer against gauge
First checks
  • Check contactor aux contact and wiring
  • Look for welded or chattering contactor
  • Verify 24 V coil supply
First checks
  • Drive powered and not in fault
  • RS-485 A/B polarity and termination
  • Check drive parameter for control source

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • Sequencing between Xe controllers is RS-485 daisy-chained — no star topology, 120 Ω at both physical ends
  • Keep transducer runs out of the starter compartment; VFD carrier noise shows as jittery pressure
Known issues & field notes
  • Display ribbon connector backs out with panel vibration — reseat before condemning the CPU
  • Firmware before 2017 mis-handles daylight-saving on scheduled start/stop

Service level is distributor-set. Operator-level parameter access needs no code on most builds.