AirCompDX - Field Reference for Air Compressor Techs

GD Pilot TS / AirSmart

Pilot TS is the current-generation controller; AirSmart is the earlier text-based system. On EnviroAire oil-free machines the controller also sequences the intercooler condensate drains — verify drain function during PM.

Manufacturer
Gardner Denver
Display
GD Pilot TS: 5.7" TFT color touch; AirSmart: 4-line VFD monochrome (older).
Years produced
Pilot TS ~2013 – present; AirSmart 2000s – 2013.
Power supply
24 VDC control power from onboard PSU. Battery-backed RTC.
Ambient range
0 – 50 °C.
Protection rating
IP54 front / IP20 rear.
Relay outputs
Configurable — main, star, delta, blowdown, dryer, alarm, remote-run, service.
Replaces
AirSmart, Auto Sentry ES (legacy)
Used on
  • Gardner Denver EnviroAire T-Series (oil-free)
  • Gardner Denver VS / VST rotary screws
  • Gardner Denver L-Series (LC / LS)
  • Gardner Denver ELECTRA-SAVER II retrofit
On AirCompDX
Features
  • Sequencing up to 12 units on Pilot TS
  • iConn cloud monitoring
  • Fine-grained pressure band control
  • Compressor + integrated dryer control on single HMI
  • Trend log to internal memory / USB export
Interfaces
  • Ethernet Modbus TCP / Profinet
  • RS-485 Modbus RTU
  • USB service port
  • Digital I/O 24 VDC
  • iConn cloud gateway (add-on)
Sensor inputs
  • Airend discharge temp (T2)
  • Package discharge pressure
  • Sump pressure
  • Separator ΔP
  • Coolant filter ΔP (option)
  • Ambient temp (option)
Common fault codes
First checks
  • Check coolant level and cooler condition
  • Verify thermostatic mixing valve
  • Test T2 sensor resistance
First checks
  • Replace separator element and fluid filter
  • Check scavenge line for clog
  • Change coolant if past hours
First checks
  • Check unload setpoint
  • Verify inlet valve closes
  • Inspect MPCV
First checks
  • Swap any two incoming phases at disconnect
  • Confirm arrow on airend matches
  • Check phase monitor relay module
First checks
  • Reset overload
  • Verify FLA and voltage balance
  • Inspect for airend drag or oil starvation
First checks
  • Clean cooler / fan
  • Check bearings & OL setting
First checks
  • Read drive keypad F-code
  • Check drive cabinet cooling filter
  • Verify DC bus discharged before service
First checks
  • Check RS-485 wiring & termination
  • Verify addresses & baud
  • Reboot iConn gateway
First checks
  • Perform kit A/B/C service
  • Reset counter in Service menu

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Wiring notes
  • 24 VDC control from onboard PSU; expansion modules on internal RS-485
  • Pilot TS supports both Y-Δ and VFD control heads with same HMI
  • Sensor cabling shielded, single-point ground at controller
Terminal & connector map

Pinouts distilled from OEM wiring diagrams. Exact silk-screen labels and pin numbering vary by hardware revision and package options — always confirm against the machine’s as-built wiring diagram before landing a wire.

Connectors to the controller
  • X1 – 24 VDC power in (screw terminals)
  • X2 – RJ45 Ethernet (Modbus TCP / iConn cloud)
  • X3 – RS-485 (Modbus RTU sequencer, up to 8 units)
  • X4 – RTD block, airend & aftercooler
  • X5 – 4–20 mA transducer block (line, sump, ΔP filter, ΔP separator)
  • X6 – digital I/O to starter + dryer + drain solenoids
  • USB port behind door – firmware update & trend export
X1 – PowerControl power
PinSignalTypeConnects to
++24 VDC24 VDCControl transformer +
0 V24 VDC ret.Control transformer −
PEPEPECabinet ground
X4 – TemperatureRTDs
PinSignalTypeConnects to
1 / 2 / 3Airend dischargePT100 3-wireAirend sensor
4 / 5 / 6Aftercooler out (option)PT100 3-wireAftercooler sensor
X5 – Pressure & ΔP4–20 mA transducers
PinSignalTypeConnects to
PL +/−Line pressure4–20 mALine transducer
PS +/−Sump pressure4–20 mASump transducer
ΔF +/−Fluid filter ΔP4–20 mAFilter ΔP transducer
ΔS +/−Separator ΔP4–20 mASep ΔP transducer
X6 – Digital I/OStarter / drains / remote
PinSignalTypeConnects to
1M / 1S / 1DStar-delta contactor coils24 VDC outContactors
Y-BDBlowdown solenoid24 VDC outBlowdown solenoid
Y-DR1/2Intercooler / aftercooler drain solenoids (EnviroAire)24 VDC outDrain solenoids
RS+/RS−Remote startdry contact inCustomer PLC
CTCommon trouble relayrelay outMaster alarm
Known issues & field notes
  • iConn cloud sync drops on stringent firewalls — whitelist connect.gardnerdenver.com
  • Touchscreen dead pixels on early revs — replace HMI module, keep configuration on USB
Retrofit notes

AirSmart → Pilot TS retrofit exists for many EnviroAire and VS units; sensor loom is compatible but connector genders vary.

Manuals & literature
Your manuals

Sign in to upload and pin your own PDF manuals to this controller.