8910DPA32 (2-pole 30 A)

Square D (Schneider) · Definite purpose · 2-pole (8910 DP family 20–90 A; Type S for NEMA)

All contactors

8910DPA32 (2-pole 30 A)

Square D (Schneider) · 8910 DPA 30 A frame

Square D's definite-purpose line — the premium option in the HVAC aisle. Distinctive vertical contact arrangement, very tolerant of dirty power and vibration.

Ratings
FLA (inductive)
30 A @ 600 V
LRA (locked rotor)
180 A @ 240 V · 150 A @ 480 V
Resistive
40 A
Single-phase HP
2 HP @ 115 V · 5 HP @ 230 V
Coil data
Available coil voltages
V02 = 24 VAC · V09 = 120 VAC · V53 = 208–240 VAC
Inrush VA
≈ 32 VA
Sealed (holding) VA
≈ 5.5 VA
Pickup voltage
≥ 85% of rated
Dropout voltage
20–60% of rated
Typical measured coil resistance (±15%, ballpark)
24 VAC (V02)≈ 10–15 Ω
120 VAC (V09)≈ 200–350 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (24 VAC (V02) table value)10 Ω15 Ω
Generic mid-frame 24 VAC4 Ω9 Ω

OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: Box lugs 14–8 AWG
Auxiliary contacts: 9999 aux contact kits available
Cross-references
Field notes
  • DPA part-number decode: 8910 DP A 3 2 V02 → A = 600 V class, 3 = 30 A size tier, 2 = poles, V02 = coil.
  • If the contactor is fine but the coil is smoked, replacement coils (9998 kits) are stocked separately.