42CF35AJ (3-pole 60 A FLA)
Heavy definite-purpose frame for three-phase compressors up to about 20 HP @ 460 V. Common OEM contactor on Champion, FS-Curtis and refrigeration packages.
- FLA (inductive)
- 60 A @ 600 V max
- LRA (locked rotor)
- 360 A @ 240 V · 300 A @ 480 V
- Resistive
- 75 A
- Three-phase HP
- ≈ 10 HP @ 230 V · 20 HP @ 460 V
- Available coil voltages
- Suffix AJ = 24 VAC; AG = 120 VAC; AF = 208–240 VAC
- Inrush VA
- ≈ 90 VA
- Sealed (holding) VA
- ≈ 9 VA
- Pickup voltage
- ≥ 85% of rated
- Dropout voltage
- 20–65% of rated
OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.
Coil resistance checker
Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.
OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.
- Eaton C25DNF360
- ABB DP60C3P
- Square D 8910DPA63 (3P version)
- On 3-phase recips check for single-phasing evidence: one pole burned while the other two are clean means it lost a leg upstream.
- Frame also comes in 50 A and 75/90 A (42E…) versions — match the FLA stamp on the label, not the silhouette.
Links go to the manufacturer's current catalog or product page — model-specific pages are often retired, so these stay live.