780 series (2-pole 40 A)

Mars / JARD · Definite purpose · 2-pole (3-pole in 781/783 series)

All contactors

780 series (2-pole 40 A)

Mars / JARD · DP 40 A frame

Wholesale-counter standard 40 A definite-purpose contactor. The 24 VAC coil version (e.g. Mars 17447/61447) is the most-stocked contactor in HVAC.

Ratings
FLA (inductive)
40 A @ 240–600 V
LRA (locked rotor)
240 A @ 240 V · 200 A @ 480 V
Resistive
50 A
Single-phase HP
3 HP @ 115 V · 7.5 HP @ 230 V
Coil data
Available coil voltages
24 VAC, 120 VAC, 208–240 VAC
Inrush VA
≈ 31–40 VA
Sealed (holding) VA
≈ 5–6 VA
Pickup voltage
≥ 85% of rated
Dropout voltage
20–65% of rated
Typical measured coil resistance (±15%, ballpark)
24 VAC≈ 8–13 Ω
120 VAC≈ 180–320 Ω

OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.

Coil resistance checker

Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.

Ω
This model (24 VAC table value)8 Ω13 Ω
Generic mid-frame 24 VAC4 Ω9 Ω

OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.

Terminals & accessories
Power/coil terminals: Box lugs accept 14–8 AWG; coil tabs are 1/4 in. quick-connects
Auxiliary contacts: Some SKUs offer a 1-SPST auxiliary switch piggyback; not universal — check the box
Cross-references
  • Packard C240A
  • Titan TPD402C
  • Eaton C25BNB240
  • Siemens 42BF35AG (3-pole cousin)
Field notes
  • Quick-connect coil terminals vibrate loose on reciprocating compressors — crimp properly and tug-test every one.
  • If the new coil burns out in days, find the cause: low control voltage, coil rated 24 V sitting on 28+ V, or mechanical binding in the armature.