DP30C2P-1 (2-pole 30 A)
ABB's definite-purpose line, widely sold through electrical distributors. Solid mid-tier option between the cheapest generics and full industrial frames.
- FLA (inductive)
- 30 A
- LRA (locked rotor)
- 180 A @ 240 V
- Resistive
- 40 A
- Single-phase HP
- 2 HP @ 115 V · 5 HP @ 230 V
- Available coil voltages
- -1 suffix = 24 VAC; also 120 V and 208–240 V coils
- Inrush VA
- ≈ 30 VA
- Sealed (holding) VA
- ≈ 5 VA
- Pickup voltage
- ≥ 85% of rated
- Dropout voltage
- 20–65% of rated
OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.
Coil resistance checker
Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.
OL = open coil. 0–2 Ω = shorted turns (often from a cooked transformer). Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.
- Same chassis size as the Packard/Mars/Eaton 30 A frames — carry one and it covers all three.
Links go to the manufacturer's current catalog or product page — model-specific pages are often retired, so these stay live.