AN16 / Freedom NEMA (Size 1, 27 A)
Eaton Freedom-series NEMA starter. Size 1, 27 A continuous. Common in packaged compressor skids and pump panels; C306 overloads dial FLA directly instead of using heaters.
- Continuous current
- 27 A
- Hp (3Φ)
- 7.5 HP @ 230 V · 10 HP @ 460/575 V
- Hp (1Φ)
- 2 HP @ 115 V · 3 HP @ 230 V
- Single-phase HP
- 2 HP @ 115 V · 3 HP @ 230 V
- Three-phase HP
- 7.5 HP @ 230 V · 10 HP @ 460/575 V
- Available coil voltages
- Coil codes: A = 120 V · B = 240 V · C = 480 V · D = 208 V · T = 24 V
- Inrush VA
- ≈ 190 VA
- Sealed (holding) VA
- ≈ 25 VA
- Pickup voltage
- ≥ 85% of rated
- Dropout voltage
- ≈ 40–65% of rated
OL = open coil · near zero = shorted turns · coil-to-frame must read >1 MΩ.
Coil resistance checker
Pick the coil voltage, enter your meter reading across A1–A2 (coil disconnected), and compare it to the expected ballpark.
Readings 2× high usually mean heat damage and a coil near end of life. Ballpark only (±15%+); electronic wide-range coils (e.g. ABB AF) read misleading values — test those at rated voltage instead. Always measure coil-to-frame too: must be >1 MΩ.
- Square D 8536 Size 1
- Allen-Bradley 509 Size 1
- Siemens Class 14 Size 1
- GE CR306
- AN16DN0AB decode: AN16 starter · D = NEMA Size 1 · N0 = NEMA 1 enclosure · A = 120 V coil · B = heater-less bimetal.
- C306 overloads have a FLA dial AND a manual/auto reset selector — check which mode it's in before blaming a 'no reset'.
Links go to the manufacturer's current catalog or product page — model-specific pages are often retired, so these stay live.