Sullivan-Palatek SP series PLC controller

Sullivan-Palatek

Sullivan-Palatek SP series PLC controller

Sullivan-Palatek panels are among the most Modbus-friendly OEM controllers — the full register map ships in the manual, which makes them easy to integrate into plant SCADA without a gateway.

Manufacturer
Sullivan-Palatek
Display
Monochrome text LCD (4-line) with tactile keypad; later builds use a small color HMI.
Years produced
~2008 – present on D-series industrial screws.
Power supply
24 VDC from the panel supply with fuse-protected I/O rails.
Ambient range
0 – 50 °C.
Protection rating
NEMA 12 typical in OEM panel.
Relay outputs
Starter command, load/unload solenoid, blowdown, fan motor, alarm beacon.
Used on
  • Sullivan-Palatek D25 – D400 industrial rotary screws
  • Some portable electric models
Features
  • Modulation / load-unload / auto-dual control selectable in menu
  • Adjustable service intervals with countdown hours
  • Event history buffer (last ~20 events)
  • Remote monitoring-ready via Modbus register map in the manual
Interfaces
  • Modbus RTU slave standard
  • Dry contacts remote start/stop
  • Optional ethernet module on HMI builds
Sensor inputs
  • Discharge temperature probe (Type J thermocouple on early builds, RTD on later)
  • Discharge pressure transducer
  • Sump pressure transducer
  • Differential pressure switches for filters
Fault code lookup
First checks
  • Oil and cooler
  • Thermal valve
  • Probe type matches controller configuration (J-thermocouple vs RTD)
First checks
  • Inlet valve operation
  • Minimum pressure valve
  • Oil level / foaming
First checks
  • Transducer calibration
  • Unloader not seating
  • Check valve leakage
First checks
  • Amp draw vs FLA
  • Voltage balance
  • Bearing condition
First checks
  • Terminal torque on the input card
  • Sensor wiring chafe points at the cabinet pass-through
First checks
  • Change indicated filter
  • Verify differential switch tubing not kinked

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • Thermocouple vs RTD selection is a controller parameter AND a hardware input — mismatch causes wildly wrong readings; verify both
  • Modbus terminals are labeled A/B/GND on the lower I/O rail
  • The alarm beacon output is fused at 2 A — do not power horns over that without an interposing relay
Known issues & field notes
  • Early J-thermocouple builds drift in high vibration — upgrade kit converts to RTD input
  • Keypad overlays cloud in wash-down environments; replacement overlays are inexpensive

Two-level access: operator and service. Service code supplied with the unit documentation packet.