Quincy QSI Series controller

Quincy

Quincy QSI Series controller

QSI controllers share the sensor family with Power$ync packages, which makes transducers easy to source even when a board is not.

Manufacturer
Quincy
Display
Backlit LCD text display with keypad and status LEDs.
Years produced
~2000 – present across QSI-series screw packages.
Power supply
24 VDC from package control transformer (115 VAC control circuit on many builds).
Ambient range
0 – 45 °C.
Protection rating
IP54 front.
Relay outputs
Star/delta or full-voltage contactors, load solenoid, blowdown, common alarm, remote-run.
Used on
  • Quincy QSI 245 – 1500 rotary screws
  • QSB / QGS larger frames on some builds
Features
  • Load/unload, modulation and auto-dual control modes
  • Adjustable unload timer and minimum run timer
  • Maintenance hour counters for fluid, filters and separator
  • Alarm history with running-hour stamps
Interfaces
  • Modbus RTU (RS-485)
  • Volt-free run/alarm contacts
  • Remote start/stop
Sensor inputs
  • Sump pressure
  • Package discharge pressure
  • Airend discharge temperature (RTD)
  • Separator ΔP (option)
  • Motor overload contact
Fault code lookup
First checks
  • Fluid level and cooler fouling
  • Thermal bypass valve
  • Verify RTD against an IR reading at the airend
First checks
  • Separator element plugged
  • Minimum pressure valve stuck
  • Inlet valve not modulating
First checks
  • Blowdown solenoid leaking through
  • Inlet valve stuck closed
  • Transducer zero with unit vented
First checks
  • Amp draw vs nameplate on all legs
  • Voltage imbalance under 2 %
  • Starter contact condition
First checks
  • Confirm with a mechanical gauge
  • Check fluid condition — wrong fluid foams and plugs elements early
First checks
  • Loop check at the terminal
  • Shield grounded one end only
  • Substitute a known-good sensor

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • 115 VAC control circuits are common on North American builds — verify the transformer tap matches actual site voltage before chasing 'random reset' complaints
  • Blowdown solenoid coil needs suppression; unsuppressed coils kill the output driver
Known issues & field notes
  • Keypad overlay lifts at the edges in humid rooms and lets moisture into the dome switches
  • Older revisions lose the alarm log on a full power-down when the backup cell is dead

Service parameters are behind a distributor code; no published universal code.