Quincy QGV variable-speed controller

Quincy

Quincy QGV variable-speed controller

On a QGV, always confirm whether the fault originated in the controller or the drive — the drive keypad carries the detailed code and the fault history the controller does not show.

Manufacturer
Quincy
Display
Backlit graphic LCD with soft keys; drive keypad separately accessible in the cabinet.
Years produced
~2005 – present on QGV variable-speed rotary screws.
Power supply
24 VDC control supply derived from the drive panel.
Ambient range
0 – 46 °C (drive cabinet ventilation is critical).
Protection rating
IP54 front, drive section IP20 internally.
Relay outputs
Drive run/enable, blowdown solenoid, dryer enable, common alarm, remote-run.
Used on
  • Quincy QGV 15 – 200 hp variable-speed packages
Features
  • Constant-pressure control with a narrow band — typically ±1.5 psi
  • Automatic soft start with no inrush penalty on repeated starts
  • Minimum and maximum speed limits protecting airend lubrication
  • Drive fault mapping into plain-language controller messages
Interfaces
  • Modbus RTU (RS-485) to the drive and to a master
  • Volt-free contacts
  • Remote pressure setpoint (option)
Sensor inputs
  • Package discharge pressure
  • Sump pressure
  • Airend discharge temp (RTD)
  • Drive heatsink temperature
  • Motor thermal contacts
Fault code lookup
First checks
  • Read the raw code on the drive keypad — the controller message is a summary
  • Overcurrent: check airend drag and drive tuning
  • Overvoltage: check decel ramp and line conditions
First checks
  • A/B polarity and termination
  • Drive control-source parameter
  • Look for VFD carrier noise coupling into the comm run
First checks
  • Cabinet filters plugged
  • Cabinet fan failed
  • Room temperature above rating
First checks
  • Fluid level and cooler fouling
  • Thermal valve
  • Extended low-speed running reduces cooling flow — check minimum speed setting
First checks
  • Minimum speed set too low
  • Blowdown leaking
  • Minimum pressure valve stuck open
First checks
  • Loop check at the terminal
  • Shielded run kept out of the drive compartment

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • Motor leads must be shielded VFD cable with the shield landed at both ends per the drive manual — this is the number one source of nuisance sensor faults
  • Never run the 4–20 mA transducer loop in the same conduit as the drive output
  • Confirm drive input reactor / line conditioning is present on soft plants
Known issues & field notes
  • Running a VSD machine at the bottom of its speed range for long periods causes coolant carryover and separator loading — set minimum speed per the manual, not lower
  • Drive cabinet filter neglect is the most common cause of repeat over-temperature trips

Controller service level is distributor-set. Drive parameters have their own separate drive-level password.