Quincy Q-Master Sequencer
Plant master for Quincy fleets. Pairs with each machine's local Power$ync II/III panel. Mixed-brand plants can be run in dry-contact mode but lose per-unit trend visibility.
Manufacturer
Quincy Compressor
Display
5.7-inch color TFT touch, membrane bezel.
Years produced
~2012 – present, multiple hardware revisions.
Power supply
24 VDC control power, 120 VAC input.
Ambient range
0 – 46 °C.
Protection rating
IP54 front (NEMA 12 wall-mount enclosure).
Relay outputs
Per-machine run/stop dry contacts, common alarm, standby, dryer enable.
Used on
- Networks of Quincy QGS / QSI / QSV rotary screws
- Mixed-brand plants via dry-contact enable
Features
- Sequences up to 12 compressors (mixed VSD + fixed)
- Equal run-hours or lead/lag priority scheduling
- Cascade or narrow-band control (adaptive on VSD-primary systems)
- Weekly / holiday scheduling with 16 events
- Event log with USB export
Interfaces
- Ethernet Modbus TCP
- RS-485 Modbus RTU
- Digital I/O terminal strip
- USB service
- Optional cellular telematics
Sensor inputs
- Common header pressure (4–20 mA)
- Ambient temp (option)
- Dewpoint (Modbus, option)
Common fault codes
First checks
- Verify cable & 120 Ω termination
- Check slave node address matches config
- Confirm unit's controller is powered and in Auto
First checks
- Verify 24 VDC loop
- Test sensor at known pressure
- Check for condensate in the pressure line
First checks
- All machines in Auto?
- Large leak or open service valve?
- Review event log for cascading trips
First checks
- Unload setpoints on each unit
- Check for a compressor stuck in load
- Inlet valve stuck open on lead unit
First checks
- Release E-stop
- Check remote loop wiring
Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.
Wiring notes
- Modbus RTU to Quincy Power$ync-equipped units — daisy-chain with 120 Ω termination at each end
- Legacy Quincy or other-brand units wire via dry-contact enable + run-feedback + fault-feedback pairs
- Header pressure sensor MUST be on the plant discharge header, downstream of all machines and the receiver
Known issues & field notes
- Ethernet port on early hardware revs sensitive to ground loops — isolate with a media converter on long runs
- Firmware < 2.10 could double-count run hours after Modbus reconnect — update recommended
Technician and Service PINs — default technician PIN is often 2222 on new commissioning; MUST be changed. Service level is Quincy-locked.