Quincy Q-Command / Q-Command 4.0 sequencer
Use the built-in trending to document unloaded run hours before and after sequencing — that report is usually what justifies the panel to the customer.
Manufacturer
Quincy
Display
Color touchscreen (Q-Command 4.0); text LCD on earlier Q-Command panels.
Years produced
~2010 – present.
Power supply
100 – 240 VAC wall-mount panel, internal 24 VDC bus.
Ambient range
0 – 50 °C.
Protection rating
NEMA 4 / IP54 enclosure options.
Relay outputs
Per-compressor enable relays, dryer enable, common alarm.
Used on
- Mixed Quincy fleets
- Third-party compressors via contact or Modbus interface
Features
- Pressure-band sequencing with rotation on run hours
- VSD trim management so only one variable machine modulates
- Energy and specific-power reporting for audits
- Scheduled pressure setpoints for off-shift savings
Interfaces
- Ethernet Modbus TCP
- RS-485 Modbus RTU
- Web dashboard on 4.0
- Email/SMS alarm notification on 4.0
Sensor inputs
- System header pressure (primary and backup)
- Flow / dew point (option)
- Per-compressor status via Modbus or dry contacts
Fault code lookup
First checks
- Unique slave address
- Bus termination at both physical ends only
- Machine must be in Remote mode
First checks
- 4–20 mA loop check
- Sense line valve closed
- Compare with calibrated gauge
First checks
- Machines locked out or in Local
- Standing alarms on slaves
- Check for a large new leak or a stuck-open drain
First checks
- Check master power and network
- Verify backup switch setpoints
Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.
Sensor pin resistance & signal values
Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.
Wiring notes
- Every slave must be switched to Remote/Sequenced at its own controller before the master can command it
- Run the Modbus trunk in dedicated conduit away from starter and VFD wiring
- Always keep a hardwired backup pressure switch as a failsafe
Known issues & field notes
- Mixing very old contact-only machines with Modbus machines needs an interface module per legacy unit
Operator and administrator levels set at commissioning by the Quincy distributor.