Quincy Q-Command / Q-Command 4.0 sequencer

Quincy

Quincy Q-Command / Q-Command 4.0 sequencer

Use the built-in trending to document unloaded run hours before and after sequencing — that report is usually what justifies the panel to the customer.

Manufacturer
Quincy
Display
Color touchscreen (Q-Command 4.0); text LCD on earlier Q-Command panels.
Years produced
~2010 – present.
Power supply
100 – 240 VAC wall-mount panel, internal 24 VDC bus.
Ambient range
0 – 50 °C.
Protection rating
NEMA 4 / IP54 enclosure options.
Relay outputs
Per-compressor enable relays, dryer enable, common alarm.
Used on
  • Mixed Quincy fleets
  • Third-party compressors via contact or Modbus interface
Features
  • Pressure-band sequencing with rotation on run hours
  • VSD trim management so only one variable machine modulates
  • Energy and specific-power reporting for audits
  • Scheduled pressure setpoints for off-shift savings
Interfaces
  • Ethernet Modbus TCP
  • RS-485 Modbus RTU
  • Web dashboard on 4.0
  • Email/SMS alarm notification on 4.0
Sensor inputs
  • System header pressure (primary and backup)
  • Flow / dew point (option)
  • Per-compressor status via Modbus or dry contacts
Fault code lookup
First checks
  • Unique slave address
  • Bus termination at both physical ends only
  • Machine must be in Remote mode
First checks
  • 4–20 mA loop check
  • Sense line valve closed
  • Compare with calibrated gauge
First checks
  • Machines locked out or in Local
  • Standing alarms on slaves
  • Check for a large new leak or a stuck-open drain

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • Every slave must be switched to Remote/Sequenced at its own controller before the master can command it
  • Run the Modbus trunk in dedicated conduit away from starter and VFD wiring
  • Always keep a hardwired backup pressure switch as a failsafe
Known issues & field notes
  • Mixing very old contact-only machines with Modbus machines needs an interface module per legacy unit

Operator and administrator levels set at commissioning by the Quincy distributor.

Manuals & literature
Quincy Compressormanuals index

Public literature library

Direct PDFs
  • Open
  • Open
  • Open
Your manuals

Sign in to upload and pin your own PDF manuals to this controller.