Xe-70M

Ingersoll Rand

Xe-70M

The Xe-70M shares transducers and RTDs with the Xe-90M/145M but has fewer I/O points and no onboard Ethernet — it is not a drop-in upgrade path.

Manufacturer
Ingersoll Rand
Display
Backlit monochrome LCD, 4-line text, 6 membrane keys with red alarm / amber warning LEDs.
Years produced
~2015 – present. Entry tier of the Xe family below Xe-90M/Xe-145M.
Power supply
24 VDC from the package control transformer (110/230 VAC primary).
Ambient range
0 – 46 °C (panel-mounted, keep out of direct airend radiant heat).
Protection rating
IP54 front / IP20 rear.
Relay outputs
Star/delta or across-the-line contactors, load solenoid, blowdown solenoid, common alarm, remote-run.
Replaces
Intellisys SG, Intellisys Simplicity
Used on
  • IR R-Series 5–30 kW fixed speed
  • UP6 / RS-Series small screw packages
Features
  • Load/unload and modulation modes with adjustable offline/online pressure
  • Auto-restart after power failure (must be enabled; ships disabled)
  • Three independent maintenance timers (filter, separator, coolant)
  • Scheduled start/stop with a 7-day timer
Interfaces
  • Modbus RTU (RS-485)
  • Volt-free run and alarm contacts
  • Remote start/stop input
Sensor inputs
  • Package discharge pressure (4–20 mA)
  • Airend discharge temperature (RTD)
  • Separator ΔP (option)
  • Motor thermal contacts
Fault code lookup
First checks
  • Coolant level and cooler core cleanliness
  • Thermostatic valve stuck in bypass
  • Verify RTD reading against an IR thermometer at the airend
First checks
  • Minimum pressure / check valve stuck open
  • Blowdown solenoid leaking through
  • Verify transducer zero with the unit stopped and vented
First checks
  • Confirm with a mechanical gauge across the separator
  • Look for coolant foaming / wrong fluid
  • Replace element and reset only that timer
First checks
  • Compare draw to nameplate FLA on all three legs
  • Voltage imbalance under 2 %
  • Airend drag / bearing noise
First checks
  • Swap any two incoming legs at the disconnect
  • Confirm phase monitor is not mis-set
  • Bump-test and watch the sheave
First checks
  • Twist-release the E-stop then press Reset
  • Jumper check the remote loop if unused
First checks
  • Loop-check the 4–20 mA at the terminal
  • Shield grounded at one end only
  • Swap in a known-good sensor

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • Pressure transducer uses a shielded 2-wire loop — grounding both ends causes drifting pressure readings
  • Blowdown and load solenoid outputs are transistor-driven; add a suppression diode across each coil
  • Remote start/stop is a dry contact only — applying 24 V to it damages the input
Known issues & field notes
  • Membrane keypad cracks at the arrow keys in hot rooms; oil mist then shorts the dome switches
  • Auto-restart ships disabled from the factory and is frequently blamed as a 'won't restart' fault

Operator menu is open. Service menu is dealer-set at commissioning; IR does not publish a universal code. If locked out, an authorized distributor must reset it.

Manuals & literature
Ingersoll Randsupport portal

Customer Care → Manuals & Parts (login often required)

Direct PDFs
  • Open
  • Open
  • Open
Your manuals

Sign in to upload and pin your own PDF manuals to this controller.