Intellisys SG / SE (legacy)

Ingersoll Rand

Intellisys SG / SE (legacy)

When quoting a repair on an SG, price the Xe retrofit alongside it — board availability is the deciding factor more often than labor.

Manufacturer
Ingersoll Rand
Display
2-line vacuum-fluorescent or LCD text display with tactile keypad.
Years produced
~1995 – 2015. Widely still in service; parts increasingly scarce.
Power supply
24 VDC from control transformer; some builds 115 VAC control circuit.
Ambient range
0 – 46 °C.
Protection rating
IP54 front panel.
Relay outputs
Star/delta contactors, load solenoid, blowdown, common alarm.
Replaced by
Xe-70M / Xe-90M
Used on
  • IR SSR / R-Series pre-2015
  • UP6 Series
  • Some Nirvana fixed-speed frames
Features
  • Online/offline and modulation control
  • Basic maintenance hour timers
  • Simple alarm history (last few events)
Interfaces
  • Volt-free run/alarm contacts
  • Optional Intellisys communication module (RS-485)
Sensor inputs
  • Sump pressure
  • Package discharge pressure
  • Airend discharge temp (thermistor/RTD)
  • Inlet vacuum switch
Fault code lookup
First checks
  • Coolant level and cooler cleanliness
  • Thermostatic valve
  • Sensor resistance check
First checks
  • Blowdown valve leaking
  • Inlet valve stuck closed
  • Transducer zero
First checks
  • Minimum pressure valve stuck
  • Separator plugged
  • Unload solenoid not shifting
First checks
  • Amp draw vs nameplate
  • Voltage imbalance
  • Starter contacts pitted

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • Control transformer taps must match site voltage — mis-tapped 208 V panels cause random resets that look like controller failure
  • Sensor grounds land on a single panel star point; daisy-chained grounds cause erratic temperature readings
Known issues & field notes
  • Vacuum-fluorescent displays dim to unreadable after ~15 years; the CPU still works
  • Original controller boards are largely obsolete — most shops now retrofit to Xe-70M/90M rather than repair

Service parameters are behind a dealer code entered from the keypad; no published universal code.