CP Central Controller (up to 6)

Chicago Pneumatic

AirCompDX - Field Reference for Air Compressor Techs

CP Central Controller (up to 6)

Multi-compressor plant master. Not a compressor controller — pairs with each machine's local panel. Best-fit for all-CP shops; mixed-brand plants often benefit from a vendor-neutral sequencer instead.

Manufacturer
Chicago Pneumatic
Display
5-inch color TFT touch.
Years produced
~2015 – present.
Power supply
24 VDC, 100–240 VAC input.
Ambient range
0 – 46 °C.
Protection rating
IP54 front.
Relay outputs
Per-machine run/stop dry contacts, common alarm, standby request.
Used on
  • Networks of CP QRS / CP screws
  • Mixed-brand plants using dry-contact enable
Features
  • Sequencing up to 6 compressors
  • Equal run-hours balancing
  • Cascade or narrow-band control
  • Trend & event export via USB
Interfaces
  • Ethernet Modbus TCP
  • RS-485 Modbus RTU
  • Digital I/O for legacy machines
  • USB service port
Sensor inputs
  • Common header pressure (4–20 mA)
  • Ambient temp (option)
  • Dewpoint from downstream dryer (Modbus)
Common fault codes
First checks
  • Check cable & termination to that unit
  • Verify slave node address
  • Cycle power to the affected unit
First checks
  • Verify 24 VDC loop
  • Test sensor at known pressure
  • Check for water in the impulse line
First checks
  • Verify all machines in Auto
  • Check for large leak or open service valve
  • Review event log for cascading trips
First checks
  • Verify unload setpoints on each unit
  • Check for a compressor stuck in load

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Wiring notes
  • Modbus RTU to CP units carrying an ES4000 or newer controller — 120 Ω termination at each end
  • Legacy IR / Sullair / GD machines wire in via dry-contact enable + run-feedback pairs
  • Header pressure sensor MUST be at the plant discharge, not on a branch
Known issues & field notes
  • USB export truncates files > 32 MB — export more often on high-event sites
  • Firmware < 1.20 mis-reports run hours after DST changes — update recommended
Manuals & literature
Chicago Pneumaticmanuals index

Parts & Services portal

Direct PDFs
  • Open
  • Open
Your manuals

Sign in to upload and pin your own PDF manuals to this controller.