BOGE focus control (1.0, original)

BOGE

BOGE focus control (1.0, original)

The original focus control shares sensor part numbers with focus control 2.0 but the CPU boards are NOT interchangeable. Upgrading a pre-2018 S-Series to 2.0 is a full panel swap, not a board swap.

Manufacturer
BOGE
Display
Monochrome graphic LCD with 6 membrane keys and LED status bar.
Years produced
~2008 – 2018. Superseded by focus control 2.0.
Power supply
24 VDC from onboard PSU (230 VAC primary on most EU packages).
Ambient range
0 – 46 °C.
Protection rating
IP54 front / IP20 rear.
Relay outputs
Main / star / delta contactors, blowdown solenoid, dryer enable, common alarm, remote-run.
Replaces
TOP control 2
Replaced by
focus control 2.0
Used on
  • BOGE S-Series (pre-2018)
  • BOGE C-Series screws
  • BOGE SD/SF packages
Features
  • Load/unload with adjustable minimum run and standstill timers
  • Base-load changeover for up to 4 compressors without a master
  • Hour and calendar service timers with 3 independent kits
  • Weekly timer / remote start-stop
Interfaces
  • RS-485 Modbus RTU
  • Volt-free alarm & run contacts
  • Optional Profibus card
Sensor inputs
  • Airend discharge temp (PT1000)
  • Sump pressure
  • Line/network pressure
  • Separator ΔP (option)
  • Motor PTC
Fault code lookup
First checks
  • Coolant level & cooler cleanliness
  • Thermostatic valve stuck open
  • PT1000 resistance ≈1385 Ω at 100 °C
First checks
  • PTC continuity (cold ≈ 100–250 Ω)
  • Motor cooling airflow
  • Check for over-frequency starts/hour
First checks
  • Verify all 3 phases at disconnect
  • Swap two incoming legs
  • Test phase-monitor relay
First checks
  • Reset OL; compare draw to nameplate FLA
  • Check voltage balance <2 %
  • Look for airend drag
First checks
  • Unload setpoint & deadband
  • Inlet valve fails to close
  • Pressure transducer drift — compare to gauge
First checks
  • Shield grounded at one end only
  • Check 4–20 mA loop at the terminal
  • Substitute known-good sensor
First checks
  • Release E-stop and reset
  • Check remote loop jumper if unused

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • 24 VDC control supply — a shared 24 V bus with the dryer is a common source of nuisance resets
  • Blowdown solenoid needs a suppression diode across the coil to protect the output transistor
  • RS-485 base-load link uses shielded twisted pair with 120 Ω terminators at each physical end
Known issues & field notes
  • LCD contrast fades and pixel rows drop after ~8–10 years of hot-room service — display is a separate service part from the CPU
  • Backup coin cell drains during long shutdowns; clock and hour meter reset on power-up
  • Membrane keypad flexes at the 'Enter' key — hairline crack lets oil mist in

Two levels: operator (setpoints) and service. BOGE dealers set these at commissioning; there is no published universal code — if the service level is locked, BOGE service must reset it.

Manuals & literature
Your manuals

Sign in to upload and pin your own PDF manuals to this controller.