BOGE connect (remote monitoring gateway)

BOGE

BOGE connect (remote monitoring gateway)

Useful for proving duty cycle and leak load before quoting a system change: pull a week of trend data instead of putting a logger on site.

Manufacturer
BOGE
Display
No local display — web / mobile dashboard.
Years produced
~2017 – present.
Power supply
24 VDC from the compressor panel.
Ambient range
0 – 50 °C.
Protection rating
DIN-rail module inside the package enclosure.
Relay outputs
None (monitoring only).
Used on
  • BOGE focus control 2.0 packages
  • airtelligence provis 3 systems
  • Retrofit to focus control 1.0 on selected frames
Features
  • Remote status, pressure, temperature and hour-meter view
  • Push alarms and service-due notifications
  • Historic trending for load profile and specific power
  • Fleet view across multiple sites
Interfaces
  • Ethernet or LTE modem to BOGE cloud
  • Modbus TCP / RTU to the machine controller
Sensor inputs
  • Reads existing controller data over the machine bus — no dedicated sensors
Fault code lookup
First checks
  • Confirm outbound HTTPS (443) is open on the plant firewall
  • LTE signal strength / SIM data plan
  • Check the gateway LED pattern against the label
First checks
  • Verify slave ID, baud, parity
  • Check A/B polarity on RS-485
  • Confirm the controller's bus port is enabled in service menu
First checks
  • Check 24 VDC supply is not shared with a switching load
  • Inspect Ethernet cable routing away from VFD leads

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • Keep the gateway's Ethernet and RS-485 runs out of the VFD compartment — drive noise is the number one cause of dropped data
  • Powering the gateway from the same 24 V rail as the blowdown solenoid causes brownout resets; use a separate fused tap
Known issues & field notes
  • Monitoring only — it cannot start, stop, or change setpoints, so it never replaces a master controller

Cloud account credentials are per-customer, issued by the BOGE dealer at activation. No local password.