BOGE airtelligence provis 3
provis is a MASTER controller, not a machine controller — each compressor keeps its own focus control or equivalent for safety shutdowns. The master only requests load/unload.
Manufacturer
BOGE
Display
10.1" color touch panel (provis 3); 5.7" on provis 2.
Years produced
provis 2 ~2012 – 2020; provis 3 ~2020 – present.
Power supply
100 – 240 VAC panel supply, internal 24 VDC bus.
Ambient range
0 – 45 °C.
Protection rating
IP54 front on wall-mount enclosure.
Relay outputs
Per-compressor enable relays, common alarm, dryer/dryer-bank enable.
Replaces
airtelligence provis 2, airtelligence 1
Used on
- Mixed BOGE fleets
- Third-party compressors via volt-free / Modbus interface
Features
- Master sequencing / band control for up to 16 compressors (4 VSD)
- Predictive load management — starts the next machine before pressure drops out of band
- Energy and specific-power reporting (kWh per 100 m³ / per 100 cfm)
- Zone pressure control with independent setpoint bands
- Leak and off-shift consumption trending
Interfaces
- Ethernet Modbus TCP
- Profinet / Profibus (option)
- RS-485 Modbus RTU
- Web browser dashboard
- BOGE connect cloud link
Sensor inputs
- Network pressure (up to 4 zones)
- Flow / dew point (option)
- Compressor status via bus or volt-free contacts
Fault code lookup
First checks
- Verify slave address is unique
- Check 120 Ω termination at both ends only
- Confirm baud/parity match at the machine controller
First checks
- 4–20 mA loop check at the master terminal
- Isolation valve on the sensing line closed?
- Compare against a calibrated gauge
First checks
- Check each unit is in REMOTE / bus mode
- Verify no local unload setpoint below the master band
- Look for a large leak or a new demand
First checks
- Read the fault at the machine controller
- Confirm the unit is enabled in the master schedule
First checks
- Check remote loop wiring / jumper
Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.
Sensor pin resistance & signal values
Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.
Wiring notes
- Wall-mounted panel — keep the Modbus trunk daisy-chained, never a star topology
- Volt-free interface for non-BOGE machines: one enable output per compressor plus a run-feedback input
- Network pressure sensor belongs downstream of the dryer and receiver, in stable flow, not on a dead leg
Known issues & field notes
- Mixing bus-controlled and contact-controlled machines can cause hunting if local unload setpoints overlap the master band — stagger local setpoints above the master band
- provis 2 web UI needs legacy Java/older browsers; provis 3 is HTML5
Operator / service / administrator levels set at commissioning. Administrator level is dealer-held.