Zero-loss (level-sensed) condensate drain

Generic / universal · Condensate drain

All components

Capacitive sensor detects condensate level and opens a pilot-operated valve only long enough to expel liquid — no compressed air lost.

Also called: no-loss drain · capacitive level drain · electronic drain

De-energised state: NC

How it works

A capacitive probe in the collection chamber signals the PCB when the chamber is full. The board energises a pilot solenoid that opens the diaphragm valve until the level probe clears, then closes before air escapes. An alarm contact is normally provided.

Coil resistance (typical, cold DC)

Coil voltageResistanceHoldInrush
24 VDC pilot30 – 60 Ω
115 VAC pilot250 – 600 Ω
230 VAC pilot1,100 – 2,400 Ω

Typical values for the stated wattage class. Always compare against the coil tag. Open circuit = burnt winding; near 0 Ω = shorted turns.

Specifications

Alarm contact
Volt-free changeover, typically 1 A @ 250 VAC
Test button
Manual open for verification
Service
Clean probe and chamber annually; oil sludge blinds the sensor

Parts you can order

  • BEKO Technologies
    BEKOMAT 31U
    BEKOMAT 31U
    $380 – $700
  • BEKO Technologies
    BEKOMAT 32U
    BEKOMAT 32U
    $500 – $950
  • JORC
    MINI MAG zero-loss drain
    MINI MAG
    $260 – $520
  • BEKO Technologies
    BEKOMAT 14 CO
    BEKOMAT 14 CO
    $420 – $900
  • nano purification
    Zero-loss condensate drain
    By model / capacity
    $250 – $600
Open the full parts database →

Field test procedure

  1. Press TEST: valve should open and close cleanly.
  2. Sludge on the probe reads as permanently full (constant cycling) or permanently empty (no discharge). Clean the chamber first.
  3. Check the alarm relay contact continuity if the machine reports a drain fault.

Symptoms & probable causes

  • Alarm LED and no discharge
    Plugged inlet, frozen line, or a coated probe.
  • Cycles every few seconds
    Probe fouled with oil/emulsion, or an internal seat leak.
More condensate drain