Industrial pilot duty · Allen-Bradley 836T / Danfoss KP-RT / Telemecanique XML
Pilot-duty pressure controls
Once the motor is above roughly 7.5 HP, or on any three-phase machine without an integrated starter, the pressure control stops carrying motor current and becomes a pilot device: it makes and breaks the contactor coil circuit or feeds a controller input. Ratings are stated in VA and control-circuit amps, not horsepower.
Specifications
- Action
- Standard — contacts open on rising pressure
- Adjustable range
- Wide — vacuum through several hundred psi depending on the sensing element
- Differential
- Adjustable on essentially all industrial pilot controls (adjustable)
- Factory settings
- Field set — these ship unset
- Ports
- 1/4 in. NPT typical; bellows, piston or diaphragm sensing depending on model and media
- Unloader
- None — unloading is handled by a separate solenoid or the compressor controller
- Lever / disconnect
- None; the starter provides hand/off/auto
- Enclosure
- NEMA 1 through NEMA 4X depending on model
- Temperature
- Model dependent
Electrical
- Pilot duty rated (VA at 120/240 VAC control voltage)
- SPDT or DPDT contacts so you can drive a coil and an alarm/telemetry input
- Never wired in series with motor leads
Size against motor full-load amps with the motor amperage calculator, and check feeder sizing with the voltage drop calculator.
Adjustment
- Set the cut-out (range) first with the machine running, then dial the differential for the starts-per-hour target.
- Check the contactor coil inrush against the switch's pilot-duty VA rating before wiring.
- On rotary screws the pressure switch is usually only a backup to the electronic controller — confirm the control philosophy before changing setpoints.
Before you open the cover
Kill power at the disconnect and lock out. Bleed the tank to 0 psi. Never set cut-out above the tank data-plate MAWP. Verify your numbers first in the cut-in / cut-out calculator.
Best fit
- Compressors above 7.5 HP
- Three-phase installs with a starter
- Plant air headers and remote-mounted controls
Watch out
- The most common failure is a technician wiring a pilot-duty switch as a power switch. It welds shut on the first start.
- On a rotary screw, adjusting a backup pressure switch will not change load/unload behaviour — that lives in the controller.
Cross-references
- Square D 9013GHG with a contactor
- Condor MDR 3 for small three-phase machines