Formula
I = (HP × 746) / (√3 × V × η × PF)Full Load Amps
12.24A
10.00 HP ≈ 7.46 kW · verify against nameplate.
Overload setting (115%)
14.08A
NEC max 125% = 15.30 A
Delta winding current
7.07A
Use this for wye-delta heater sizing.
How to use this calculator
Compute single- and three-phase motor current from horsepower, voltage, efficiency and power factor.
- Enter motor horsepower or kW and select single- or three-phase.
- Enter supply voltage.
- Enter efficiency and power factor, or accept the typical defaults.
- Compare the calculated current with the measured amps and the nameplate FLA.
Frequently asked questions
- What is the formula for three-phase motor amps?
- I = (HP × 746) ÷ (1.732 × V × efficiency × power factor). A 10 hp, 460 V motor at 90% efficiency and 0.85 PF draws about 12 A.
- Should I size overloads on nameplate FLA or the NEC table?
- Overload protection is set from the motor nameplate FLA; the NEC table values are used for conductor and branch-circuit sizing.
- What does high amp draw on one leg mean?
- More than about 10% current imbalance between legs usually points to supply voltage imbalance, a loose connection, or a shorted winding.