KP 35/36 and RT series pressure controls

Adjustable pilot-duty controls for plant air and refrigeration circuits

All pressure switches
Danfoss · KP / RT

KP 35/36 and RT series pressure controls

Danfoss KP and RT pressure controls are pilot devices with independent range and differential scales and a convertible manual/auto reset. They appear on plant air headers, dryer circuits and refrigerated dryer high/low protection.

Specifications

Action
Standard — contacts open on rising pressure
Adjustable range
Model dependent, from vacuum to about 250 psi (RT builds higher)
Differential
Adjustable, scaled in bar/psi on the faceplate (adjustable)
Factory settings
Field set — shipped unset
Ports
1/4 in. flare or 1/4 in. NPT depending on build
Unloader
None
Lever / disconnect
None; reset button on manual-reset builds
Enclosure
IP30 to IP66 depending on model
Temperature
Model dependent

Electrical

  • Pilot duty, SPDT contacts
  • Typical 10 A resistive at 250 VAC; check the VA rating against the contactor coil inrush
  • Manual or automatic reset builds

Size against motor full-load amps with the motor amperage calculator, and check feeder sizing with the voltage drop calculator.

Adjustment

  1. Set range first with a calibrated gauge on the sensing line, then the differential, then recheck range.
  2. Use manual reset for any safety function such as high discharge pressure.
Before you open the cover

Kill power at the disconnect and lock out. Bleed the tank to 0 psi. Never set cut-out above the tank data-plate MAWP. Verify your numbers first in the cut-in / cut-out calculator.

Best fit

  • Refrigerated dryer high/low protection
  • Plant header control piloting a starter

Watch out

  • These are pilot devices — never run motor current through them.
  • Manual-reset builds will not restart the plant after a trip until someone presses the button. That is the point; do not convert it to auto to silence a nuisance trip.

Cross-references

  • Allen-Bradley 836T
  • Telemecanique XML

Manufacturer documents