Quincy Power$ync II / III

Quincy Compressor

Quincy Power$ync II / III

Quincy branded units built by Atlas Copco after the 2009 acquisition share many Elektronikon-style sensor layouts, but keep OEM-specific fluid (QuinSyn) and separator part numbers.

Manufacturer
Quincy Compressor
Display
Power$ync III: 4.3" color touch; Power$ync II: 4-line LCD.
Years produced
Power$ync II ~2010 – 2018; Power$ync III ~2018 – present.
Power supply
24 VDC control power, 120/230 VAC input.
Ambient range
0 – 46 °C.
Protection rating
IP54 front.
Relay outputs
Main / star / delta, blowdown, dryer, alarm, remote-run.
Replaces
Power$ync (original)
Used on
  • Quincy QGS 5–200
  • Quincy QSI-series two-stage rotary screw
  • Quincy QSV variable-speed
On AirCompDX
Features
  • Native sequencing up to 8 units
  • Weekly timer, remote start/stop, dryer control
  • Trend log and event history
Interfaces
  • Ethernet Modbus TCP
  • RS-485 Modbus RTU
  • USB service port
Sensor inputs
  • Airend discharge temp
  • Sump pressure
  • Line pressure
  • Fluid filter ΔP
  • Separator ΔP
Fault code lookup
First checks
  • Check fluid level & cooler cleanliness
  • Verify thermal valve opens
  • Check fan operation
First checks
  • Replace separator element
  • Change fluid & filter
  • Inspect scavenge line orifice
First checks
  • Reset overload; verify FLA class 20/30
  • Check voltage & balance
  • Check for airend drag
First checks
  • Verify all 3 phases at disconnect
  • Inspect contactor & fuses
  • Check phase monitor
First checks
  • Check unload setpoint & deadband
  • Verify inlet valve closes
First checks
  • Check wiring; test sensor against reference

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • 24 VDC control from onboard PSU
  • 120 VAC contactor coils typical
Known issues & field notes
  • Ethernet port can be flaky on early II units — use RS-485 for sequencing where possible
Field tips (web-sourced)

Distilled from public OEM manuals and community technician references. Cross-check the on-machine service manual before commissioning.

Menu / access
  • F1 from the main screen → parameter menu (load/unload setpoints, timers).
  • F2 from the main screen → Diagnostic Menu (live pressures, temps, network status).
  • 'Network Diagnostic Menu 1' (F2 then next) shows sequencing peers, error count and network average pressure.
Field gotchas
  • Two-stage QSD packages report Stage 1 and Stage 2 discharge temps separately — an interstage-cooler fouling shows as high Stage 2 IN temp with normal Stage 1 OUT.
  • 'Compressor not ready' at start almost always means the auxiliary contactor (M1a) is not feeding the ready input — check the interlock loop before the controller.
  • Power$ync II network runs on RS-485 twisted pair — reversing A/B produces 'Network errors > 0' with no other symptom.