Sigma Control (original)

Kaeser

Sigma Control (original)

Sigma Control 1 and Sigma Control 2 are not interchangeable — the sensors, harness and panel cutout all change. Plan a panel rebuild, not a board swap.

Manufacturer
Kaeser
Display
Monochrome text LCD with function keys and status LEDs; industrial-PC based.
Years produced
~1998 – 2011. Superseded by Sigma Control 2.
Power supply
24 VDC internal from 230 VAC control transformer.
Ambient range
0 – 45 °C.
Protection rating
IP54 front.
Relay outputs
Main/star/delta, inlet valve solenoid, venting valve, dryer, common alarm.
Replaced by
Sigma Control 2
Used on
  • Kaeser BSD / CSD / DSD / ESD (1998–2011)
  • AS / SK / SM packages of that era
Features
  • DUAL / QUADRO / VARIO / CONTINUOUS control modes
  • Maintenance counters for filter, separator, fluid, motor bearings
  • Base-load changeover for up to 4 units
Interfaces
  • Profibus DP (option)
  • Modbus RTU (option)
  • Sigma Air Manager link
  • Volt-free contacts
Sensor inputs
  • Airend discharge temp (PT100)
  • Internal pressure
  • Network pressure
  • Motor PTC
  • Filter ΔP (option)
Fault code lookup
First checks
  • Fluid level and cooler fouling
  • Thermostatic valve
  • PT100 ≈138.5 Ω at 100 °C
First checks
  • PTC continuity cold
  • Amp draw vs FLA
  • Starts per hour over limit
First checks
  • Inlet valve not closing
  • Venting valve fault
  • Sensor drift vs gauge

Fault list is non-exhaustive and firmware-dependent. Always confirm against the controller’s on-screen help or OEM manual.

Sensor pin resistance & signal values

Pin-level resistance and signal values for the sensor types this controller uses. Works offline. De-energise the panel and lift one lead before ohming any element.

Wiring notes
  • The controller is a hardened PC — pulling power without a controlled shutdown can corrupt the CF card holding parameters
  • Profibus and sensor cabling must be routed clear of the starter compartment
Known issues & field notes
  • Compact-flash parameter card degrades with age; symptoms are random parameter loss or a controller that will not boot
  • Keypad membrane and LCD backlight are the two most common wear parts

Operator menu is open; service menus need a Kaeser service code issued by the dealer. No published universal code.