Formula
Subcool = Bubble-point Temp (from P/T) − Measured Liquid Line TempPick the refrigerant; the bubble point (liquid side) is looked up from its PT chart. Target subcool is on the equipment data plate (typ. 8–12°F).
Pressure basis
Rounding
Refrigerant
Saturation temp
83.6°F
R-410A @ 250.0 psig (250.0 psig)
Actual subcool
-11.4°F
Target 10.0°F · -21.4°F vs. target
Undercharged — low subcool means refrigerant flashing in liquid line. Find leak before adding. Negative subcool = no liquid at metering device. Check charge immediately.
How to use this calculator
Determine liquid line subcooling from head pressure and liquid line temperature.
- Select the refrigerant and enter liquid line pressure with the correct psig/psia basis.
- Enter the liquid line temperature at the condenser outlet.
- Read subcooling as saturation (bubble point) temperature minus liquid temperature.
- Compare against the manufacturer's target, typically 8–12 °F.
Frequently asked questions
- What is normal subcooling?
- Most TXV systems target 8–12 °F of subcooling at the condenser outlet; always follow the data plate when it specifies a value.
- What does low subcooling indicate?
- Low or zero subcooling generally means undercharge or a liquid line restriction; the condenser is not fully filling with liquid.
- What does high subcooling indicate?
- High subcooling usually means overcharge, a restricted metering device, non-condensables, or a dirty or airflow-restricted condenser.