Leak search, evacuation, and recharge

Repair

All guides
Repair· Advanced 2–4 hr

Complete refrigerant service after finding a leak.

Tools
Recovery machine · Recovery cylinder · Electronic leak detector · Vacuum pump · Micron gauge · Refrigerant scale · Brazing kit · Nitrogen
1

Recover to per-EPA levels

Recover to 0 psig on high-pressure systems.

SafetyEPA 608 required. Never vent.
2

Locate leak

Nitrogen pressure test at 150 psig with soap or electronic detector.

3

Repair

Braze with nitrogen purge to prevent scale.

4

Change drier

Always install a fresh liquid-line filter-drier after opening.

5

Evacuate

Pull to <500 µm with core-removal tools, decay test <1000 µm in 10 min.

6

Weigh in charge

Charge by weight per data plate; adjust with superheat/subcool at rated conditions.

Reference PDFs

in-app preview · thumbnails · search
Open
US EPA
Open
ENERGY STAR / EPA
Open
ENERGY STAR / EPA
Open
ENERGY STAR / EPA
Open
US Dept. of Energy
Open
US EPA