Weak airflow at supply registers

Airflow

AirCompDX - Field Reference for Air Compressor Techs
All HVAC symptoms
1

Clogged filter or blocked return

low
CheckPull filter. Measure return static with manometer (target <0.25" wc on residential).
FixReplace filter, open returns, add return drop if chronically high static.
ToolsManometer
2

Dirty blower wheel

med
CheckInspect squirrel-cage blades — dust caking reduces CFM dramatically.
FixPull blower, clean wheel with degreaser and brush.
3

ECM motor module fault

med
CheckVariable-speed ECM: stat call, no ramp. Check 24 V signal at motor harness.
FixReplace motor module (separate from rotor on most Genteq ECMs).
Safety

Pull the disconnect and lock out before opening HVAC equipment. Discharge dual-run capacitors before handling. Refrigerant recovery and brazing require EPA 608 certification and proper PPE.