1
Clogged filter or blocked return
lowCheckPull filter. Measure return static with manometer (target <0.25" wc on residential).
FixReplace filter, open returns, add return drop if chronically high static.
ToolsManometer
2
Dirty blower wheel
medCheckInspect squirrel-cage blades — dust caking reduces CFM dramatically.
FixPull blower, clean wheel with degreaser and brush.
3
ECM motor module fault
medCheckVariable-speed ECM: stat call, no ramp. Check 24 V signal at motor harness.
FixReplace motor module (separate from rotor on most Genteq ECMs).
Safety
Pull the disconnect and lock out before opening HVAC equipment. Discharge dual-run capacitors before handling. Refrigerant recovery and brazing require EPA 608 certification and proper PPE.