1
Dirty condenser coil
medCheckVisual + delta-T across coil >30°F.
FixWash coil; comb fins.
2
Non-condensables (air) in system
highCheckStanding pressure higher than saturation for ambient by >10 psi after long off-cycle.
FixRecover, deep evacuate to 500 µm, weigh in virgin refrigerant.
ToolsMicron gauge · Vacuum pump · Refrigerant scale
3
Overcharge
medCheckSubcool well above target (typ. 8–12°F).
FixRecover slowly until subcool in spec.
Safety
Pull the disconnect and lock out before opening HVAC equipment. Discharge dual-run capacitors before handling. Refrigerant recovery and brazing require EPA 608 certification and proper PPE.