1
Cracked / open hot-surface igniter
highCheckOhm HSI cold — typical 40–90 Ω (Norton) or 50–200 Ω (mini). Open = bad.
FixReplace HSI; never touch element with bare fingers.
ToolsMultimeter
2
No gas / closed valve
criticalCheckManual valve open; inlet pressure 5–7" WC NG, 11–14" WC LP.
FixOpen valve; call utility if no gas at meter.
SafetySmell gas? Evacuate and call utility.
3
Pressure switch not closing
medCheckInducer running but PS open; check tubing for water, cracks.
FixClear vent, drain condensate trap, replace PS if inducer draw within spec.
4
Bad control board / flame sensor after ignition
medCheckIgnites then drops out in <7 sec = flame sensor. µA on sensor <0.5 = clean/replace.
FixClean flame rod with fine Scotch-Brite (not sandpaper); replace if still low.
Safety
Pull the disconnect and lock out before opening HVAC equipment. Discharge dual-run capacitors before handling. Refrigerant recovery and brazing require EPA 608 certification and proper PPE.