Plugged condensate drain
highCheckStanding water in secondary pan or float switch tripped.
FixVacuum from outside termination; flush with warm water and vinegar (not bleach on metal pans).
ToolsWet/dry vac · Vinegar
2
Missing / dry trap
medCheckTrap on draw-through unit missing or dry — air breaks the seal.
FixInstall P-trap sized per manufacturer; prime with water.
3
Frozen coil dumping on thaw
medCheckSee ac-freezing-up.
FixAddress underlying freeze cause.
Safety
Pull the disconnect and lock out before opening HVAC equipment. Discharge dual-run capacitors before handling. Refrigerant recovery and brazing require EPA 608 certification and proper PPE.