1
Slugging (liquid refrigerant returning)
highCheckCold, sweating suction line all the way to compressor; low superheat.
FixCorrect overcharge, verify TXV bulb strapped and insulated, check for defrost stuck in cool mode.
2
Broken mounting grommets / loose panels
lowCheckPanels vibrate; compressor tilted.
FixReplace rubber isolator grommets; tighten fasteners.
3
Failed internal valves (recip)
criticalCheckHigh suction, low head, low amps.
FixCompressor replacement.
Safety
Pull the disconnect and lock out before opening HVAC equipment. Discharge dual-run capacitors before handling. Refrigerant recovery and brazing require EPA 608 certification and proper PPE.