Branch breaker trips or motor overload kicks during start or run.
1
Locked rotor / seized airend or pump
criticalCheckLockout/tagout, then bar over by hand. Should rotate freely.
FixIf seized, airend rebuild or pump replacement required. Do not attempt to free with power.
SafetyLOTO before any rotational check. Stored air pressure must be bled to 0 PSI.
Sign in to rate whether this fix helped.
2
Single-phasing (3Φ)
highCheckMeasure all three legs at motor under load; check phase loss relay.
FixRestore lost phase; check fuses, contactor tips, terminations.
ToolsMultimeter · Clamp meter
Sign in to rate whether this fix helped.
3
Low supply voltage
CheckVoltage at motor terminals under load — must be within ±10% of nameplate.
FixCorrect supply; check wire size and length (voltage drop). Use voltage-drop calculator.
ToolsMultimeter · Clamp meter
Sign in to rate whether this fix helped.
4
Voltage imbalance >2%
Rotary screw
CheckMeasure L1-L2, L2-L3, L1-L3. Imbalance = (max deviation / avg) × 100.
FixHave utility/electrician balance phases. NEMA guidance: current imbalance can run 6–10x the voltage imbalance percentage, causing disproportionate winding heating.
Sign in to rate whether this fix helped.
5
Wrong overload setting
CheckOL set to 115–125% of motor FLA on nameplate.
FixReset dial / select correct heater element.
Sign in to rate whether this fix helped.
6
Discharge pressure above setpoint
CheckVerify pressure switch / load setpoint; verify unloader function.
FixAdjust setpoint; repair unloader.
Sign in to rate whether this fix helped.
7
Motor winding short / ground fault
criticalCheckMegger windings to ground with a 500V or 1000V megohmmeter appropriate to motor voltage class (IEEE 43 minimum acceptable ≈1 MΩ + 1 MΩ per kV rating; a healthy motor typically reads >100 MΩ). Compare to OEM baseline.
FixRewind or replace motor.
ToolsMegohmmeter (500V or 1000V)
SafetyDischarge windings to ground after meggering.
Sign in to rate whether this fix helped.
8
Starting too frequently (recip)
Reciprocating
CheckCount starts/hour. Recip motors generally allow 6–10 starts/hr max.
FixAdd storage receiver; widen pressure differential.
Sign in to rate whether this fix helped.
9
Inrush during start (recip without unloader)
Reciprocating
CheckVerify centrifugal unloader or pilot unloader releases head pressure on shutdown.
FixRepair pilot/unloader valve so the next start is unloaded.
Sign in to rate whether this fix helped.
10
Capacitor failed (single-phase)
Reciprocating
CheckTest start/run cap with capacitance meter. Must be within ±10% of rating.
FixReplace cap with same μF and ≥ original VAC rating.
ToolsCapacitance meter
Sign in to rate whether this fix helped.
Did we solve your issue?
Sign in to share what resolved it and help others.
Field notes & discussion (0)
Share what actually fixed it. Comments are reviewed by a moderator before they go public.
Sign in to join the discussion.
Safety
Lockout/tagout before opening enclosures. Verify zero energy. Bleed system pressure before opening any pneumatic connection.