Controller shows an impossible temperature or pressure

Controls

All symptoms

Reads −40°F, 999, open-circuit or a value that will not move.

1

Open or shorted RTD / thermistor

med
CheckDisconnect and measure the element: a PT100 reads ~100Ω at 32°F, a PT1000 ~1000Ω. Open circuit shows infinity.
FixReplace the sensor; check the wiring for chafe and moisture in the connector.
ToolsMultimeter
Sign in to rate whether this fix helped.
2

4–20 mA loop broken or mis-scaled

med
CheckRead loop current in series: 4 mA = sensor zero, 20 mA = full scale. Under 3.6 mA is a broken loop.
FixRepair the loop or correct the scaling parameters in the controller.
ToolsMultimeter with mA range
Sign in to rate whether this fix helped.
3

Ground loop / VSD noise on the signal cable

med
CheckNote whether the reading is only unstable while the drive runs; confirm the shield is grounded at one end only.
FixRe-route signal cable away from motor leads, use shielded twisted pair, ground the shield at the panel end only.
Sign in to rate whether this fix helped.
4

Blocked or wet pressure sense line

low
CheckCrack the sense line fitting and check for oil or water; compare against a test gauge.
FixClear and re-route the line so it drains back; add a snubber where pulsation is high.
Sign in to rate whether this fix helped.