Moisture found in instrument air system

Air quality

All symptoms

Instrument air quality fails to meet ISA/ANSI dewpoint requirements, risking valve/actuator icing or malfunction.

1

Dewpoint above required margin below minimum ambient temperature

CheckInstrument air standards (e.g., ISA-7.0.01) call for pressure dewpoint at least 18°F (10°C) below the lowest expected ambient/piping temperature — verify actual dewpoint against this margin.
FixService or upsize dryer; verify dryer sized for actual flow and inlet conditions.
Sign in to rate whether this fix helped.
2

Desiccant dryer purge flow/pressure incorrect

CheckVerify purge orifice size and regen cycle time against OEM spec.
FixCorrect orifice/purge settings per manual.
Sign in to rate whether this fix helped.
3

Coalescing/particulate filters not maintained downstream of dryer

CheckCheck ΔP and element service life on point-of-use filtration.
FixReplace filter elements on schedule.
Sign in to rate whether this fix helped.
4

Long uninsulated piping runs through cold areas causing condensation downstream of dryer

CheckTrace piping route for unheated/outdoor sections.
FixInsulate or heat-trace piping, or add point-of-use drying.
Sign in to rate whether this fix helped.

Did we solve your issue?

Sign in to share what resolved it and help others.

Field notes & discussion (0)

Share what actually fixed it. Comments are reviewed by a moderator before they go public.

Sign in to join the discussion.
Safety

Lockout/tagout before opening enclosures. Verify zero energy. Bleed system pressure before opening any pneumatic connection.