Refrigerated Dryer Capacity Correction

All calculators
Formula
Actual SCFM = Nameplate × F(inlet T) × F(inlet P) × F(ambient T)
Nameplate SCFM is rated at 100°F inlet air, 100 psig, 100°F ambient. Hot/low-pressure conditions cut real capacity sharply.
Corrected capacity
166scfm
Combined factor 0.83 × nameplate
Correction factors used
Inlet temp factor0.85
Inlet pressure factor0.96
Ambient temp factor1.02
Capacity loss > 15%. If this dryer follows a compressor at full load, expect wet air downstream. Add headroom or improve cooling.
Field notes
  • Inlet temp is the air leaving the aftercooler — not shop ambient.
  • Every 5°F above 100°F inlet drops capacity ~10–15%.
  • At 80 psig dryers run at ~92% of 100 psig capacity.
  • Hot mechanical rooms throttle the condenser — fix airflow first.

How to use this calculator

Apply inlet temperature, ambient and pressure correction factors to a dryer's rated capacity.

  1. Enter the dryer's nameplate rated flow.
  2. Enter actual inlet air temperature, ambient temperature and operating pressure.
  3. Read the corrected capacity after all derating factors.
  4. Verify the corrected capacity still exceeds peak system demand.

Frequently asked questions

Why must dryer capacity be derated?
Ratings are published at standard conditions (typically 100 psig, 100 °F inlet, 100 °F ambient). Hotter inlet air, hotter ambient or lower pressure all cut real capacity, sometimes by 30% or more.
How much does low pressure hurt dryer capacity?
Lower pressure means higher actual volume for the same mass, so a dryer at 80 psig handles noticeably less SCFM than the same unit at 100 psig.
Should the dryer be sized on peak or average flow?
Size on peak flow at the worst-case summer inlet and ambient temperatures, not on average demand.